2022-08-01 14:12:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST:
  
 2. THIS BUILDING HAS A 7" SLAB, SOUND TEST FOR AN 8"
 SLAB WAS SUBMITTED. THE STC/IIC NEEDS TO BE TESTED WITH
 A 7" OR THINNER SLAB, SEE COMMENT #3.
  
 3. SEE PREVIOUS LIST FOR CODE REFERENCES
  
 PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD. PROFLEX MAXXIM 90
 IS PROPOSED, WE DO NOT HAVE THOSE TEST REPORTS ON FILE.
 EITHER SELECT A PRODUCT FOR WHICH WE HAVE TEST REPORTS
 ON FILE, OR PROVIDE THE FOLLOWING:
  
 A, B. STC/IIC - RESPONSE LETTER STATES THAT WAS ALREADY
 SUBMITTED. THAT TEST REPORT WAS DONE WITH AN 8" SLAB.
 THIS UNIT HAS A 7" SLAB.
  
 C. FLAME SPREAD - 2ND REVIEW, TEST REPORT IS FOR
 SUPERSIM 90, NOT MAXXIM 90.
  
 IF YOU WOULD LIKE TO CHANGE THE PRODUCT PROPOSED FROM
 PROFLEX MAXXIM 90 TO SUPERSIM 90, REVISE PLAN. TEST
 REPORTS THAT WE HAVE ON FILE WILL BE UPLOADED FOR YOU.