2022-08-06 10:57:37 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. OK |
| |
| 2. FS471, ENGINEER DOES NOT HAVE A DIGITAL OR |
| ELECTRONIC SIGNATURE - HE CAN SUBMIT ONE SIGNED AND |
| SEALED PAPER ORIGINAL AFTER ALL REVIEWS HAVE PASSED. |
| |
| 3. FBC B 1207 (ALSO SEE PREVIOUS LIST FOR MORE COMPLETE |
| CODE REFERENCES AND GUIDANCE). BASED ON THE FILES |
| UPLOADED, NUCORE FLOORING IS PROPOSED OVER SHAW |
| GROUNDWORKS UNDERLAYMENT. |
| |
| FLAME SPREAD FOR GROUNDWORKS - IS OK. |
| |
| THE STC/IIC FOR GROUNDWORKS WAS DONE WITH SMARTCORE PRO |
| FLOORING. SINCE LVT HAS A STC/IIC VALUE, IT IS NOT |
| CLEAR IF THE FLOORING PROPOSED COMPLIES WITH THE |
| MINIMUM REQUIREMENTS OF STC/IIC. EITHER PROVIDE AN |
| ENGINEERED ANALYSIS OF NUCORE VS. SMARTCORE, OR PROVIDE |
| TEST REPORTS FOR STC/IIC FOR THIS ASSEMBLY, OR PROPOSE |
| A DIFFERENT PRODUCT. |
| |
| YOU MAY EMAIL THE PROPOSED RESOLUTION PRIOR TO |
| RESUBMITTING IF YOU WOULD LIKE. ALTHOUGH THIS REVIEW IS |
| BEING DONE WITHIN A DAY OF RESUBMITTAL, THIS IS NOT |
| TYPICAL. OUR TARGET IS 10-14 DAYS. |
| |
| |
| |
| FOR REFERENCE ONLY, THE FOLLOWING FILES WERE SUBMITTED |
| FOR FLOORING: |
| |
| SHAW GROUNDWORKS UNDERLAYMENT FLAME SPREAD (FILE NAME |
| INTERTEK FLAME SPREAD TEST REPORT) |
| NUCORE FLOORING SPEC SHEET |
| SMARTCORE PRO STC/IIC (FILE NAME SHAW INDUSTRIES VINYL |
| PLANK TEST REPORT) |
| |
| |
| |
| |