Plan Review Notes For Permit 22061580 |
Permit Number |
22061580 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-07-18 13:21:05 | SHORING AND POST TENSIONED | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING PT01 SAYS "NOT FOR CONSTRUCTION" CANNOT HAVE | | THAT STATEMENT ON THE DRAWINGS. | | | | 2) BUILDING DESIGNER OF RECORD STAMP ON THE SHORING | | SHOP DRAWINGS SAYS -"MAKE CORRECTIONS AS NOTED" NEEDS | | TO BE MARKED "NO EXCEPTION TAKEN". | | | | 3) POST - TENSIONED TENDONS - DRAWING AND CALCS NEED TO | | BE REVIEWED AND MARKED APPROVED BY THE BUILDING | | DESIGNER OF RECORD. FBC WPB 107.3.4 | | |
|