Plan Review Notes For Permit 22061546 |
Permit Number |
22061546 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2022-11-02 10:13:52 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | GARAGE HAS NOW BEEN SEPARATED FROM HOUSE AND IS A | | SEPARATE STRUCTURE AND HAS TO COMPLY WITH 225.31, | | 250.32 | | | | 225.30 NUMBER OF SUPPLIES. | | | | A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A | | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE | | DISCONNECTING MEANS | | SHALL BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT | | UNLESS PERMITTED IN 225.30(A) THROUGH (E). FOR THE | | PURPOSE OF THIS | | SECTION, A MULTIWIRE BRANCH CIRCUIT SHALL BE CONSIDERED | | A SINGLE CIRCUIT. | | | | 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) | | OR BRANCH CIRCUIT(S). | | (A) GROUNDING ELECTRODE. | | | | BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR | | BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR | | GROUNDING ELECTRODE | | SYSTEM INSTALLED IN ACCORDANCE WITH PART III OF ARTICLE | | 250. THE GROUNDING ELECTRODE CONDUCTOR(S) SHALL BE | | CONNECTED IN | | ACCORDANCE WITH 250.32(B) OR (C). WHERE THERE IS NO | | EXISTING GROUNDING ELECTRODE, THE GROUNDING | | ELECTRODE(S) REQUIRED IN | | 250.50 SHALL BE INSTALLED. |
|