2022-11-02 10:13:52FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 GARAGE HAS NOW BEEN SEPARATED FROM HOUSE AND IS A
 SEPARATE STRUCTURE AND HAS TO COMPLY WITH 225.31,
 250.32
  
 225.30 NUMBER OF SUPPLIES.
  
 A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS
 SHALL BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT
 UNLESS PERMITTED IN 225.30(A) THROUGH (E). FOR THE
 PURPOSE OF THIS
 SECTION, A MULTIWIRE BRANCH CIRCUIT SHALL BE CONSIDERED
 A SINGLE CIRCUIT.
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S).
 (A) GROUNDING ELECTRODE.
  
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE
 SYSTEM INSTALLED IN ACCORDANCE WITH PART III OF ARTICLE
 250. THE GROUNDING ELECTRODE CONDUCTOR(S) SHALL BE
 CONNECTED IN
 ACCORDANCE WITH 250.32(B) OR (C). WHERE THERE IS NO
 EXISTING GROUNDING ELECTRODE, THE GROUNDING
 ELECTRODE(S) REQUIRED IN
 250.50 SHALL BE INSTALLED.