Plan Review Notes For Permit 22061546 |
Permit Number |
22061546 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-07-28 14:28:10 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) OUTLLETS MISSING IN THE FOLLOWING ROOMS103, 205, | | 207, 210 | | | | | | SPACING. RECEPTACLES SHALL BE INSTALLED SUCH THAT NO | | POINT | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL | | SPACE IS | | MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE OUTLET. | | | | WALL SPACE. AS USED IN THIS SECTION, A WALL SPACE SHALL | | INCLUDE THE FOLLOWING: | | (1) ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING | | SPACE MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE | | FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS, | | FIREPLACES, | | AND FIXED CABINETS THAT DO NOT HAVE COUNTERTOPS OR | | SIMILAR | | WORK SURFACES. | | | | 2) THE FOLLOWING ARE REQUIRED TO BE SEPARATE PERMITS. | | | | GENERATORS, POOLS, LOW VOLTAGE SYSTEMS |
|