2022-07-28 14:28:10FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) OUTLLETS MISSING IN THE FOLLOWING ROOMS103, 205,
 207, 210
  
  
 SPACING. RECEPTACLES SHALL BE INSTALLED SUCH THAT NO
 POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS
 MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE OUTLET.
  
 WALL SPACE. AS USED IN THIS SECTION, A WALL SPACE SHALL
 INCLUDE THE FOLLOWING:
 (1) ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING
 SPACE MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE
 FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES,
 AND FIXED CABINETS THAT DO NOT HAVE COUNTERTOPS OR
 SIMILAR
 WORK SURFACES.
  
 2) THE FOLLOWING ARE REQUIRED TO BE SEPARATE PERMITS.
  
 GENERATORS, POOLS, LOW VOLTAGE SYSTEMS