Plan Review Notes
Plan Review Notes For Permit 22061540
Permit Number 22061540
Review Stop M
Sequence Number 2
Notes
Date Text
2022-09-30 07:47:282ND CYCLE REVIEW:
 PLEASE SEE 1ST CYCLE COMMENTS BELOW. IT ISN'T CLEAR
 WHAT WAS DONE WITH THE GARAGE DOOR BUT THE ENERGY
 CALCULATIONS SUBMITTED ON 9/26/2022 DOES NOT SHOW ANY
 DOORS IN THE CALCULATIONS. IF THIS ORIGINAL GARAGE WAS
 CONVERTED THEN YOU MUST APPLY FOR A BUILDING PERMIT
 WITH A CHANGE OF USE AND PROVIDE DRAWINGS FOR THIS.
 THE DIGITAL SIGNATURE OF KAREN OLIVER HAS BEEN ALTERED
 AND IS NO LONG A VALID DIGITAL SIGNATURE. PLEASE SUBMIT
 AN UNALTERED DRAWING WITH HER DIGITAL SIGNATURE.
  
 1ST REVIEW FMC
 PERMIT: 22061540
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 OUR RECORDS INDICATE THAT THIS BUILDING WAS BUILT AS A
 2 STORY BUILDING WITH A 2 CAR GARAGE WITH A CONDITIONED
 RECREATION ROOM ABOVE. IF THE USE OF THE GARAGE IS
 GOING TO BE CHANGED TO LIVING SPACE A CHANGE OF USE
 WILL NEED TO BE SUBMITTED WITH A PERMIT AND DRAWINGS
 SHOWING ALL WORK. IF THE MECHANICAL SYSTEM PROPOSED IS
 FOR DEHUMIDIFICATION ONLY THEN PROVIDE DEHUMIDIFICATION
 SYSTEMS AND PLANS SHOWING THIS. IF THE SPACE IS TO BE
 CONDITIONED WITH AC AND OR HEAT THEN THE CHANGE OF USE
 WITH DOCUMENTS WILL BE REQUIRED. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  