2022-08-29 13:53:45 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) ON SHEET CVR THE EXPOSURE CATEGORY IN SPECIFIED AS |
| C. THIS BUILDING IS LOCATED IN EXPOSURE CATEGORY D. FBC |
| 1609.4.3 |
| |
| 2) ON SHEET CVR, THE OCCUPANCY TYPE UNDER THE BUILDING |
| CODE IS R-2. THE MF32 IS A ZONING DESIGNATION. FBC |
| 310.4 |
| |
| 3) A DATA SHEET FOR DUROCK WAS SUBMITTED. THE SCOPE OF |
| WORK ON THE PLANS DOES NOT SPECIFY WHERE THE DUROCK |
| WILL BE INSTALLED. PLEASE CLARIFY. FBC 107.2.1 |
| |
| 4) THE FLAME SPREAD AND SMOKE DEVELOPED TEST REPORT FOR |
| WHISPERMAT CS WAS SUBMITTED. PLEASE SUBMIT THE |
| WHISPERMAT CS TEST REPORTS FOR THE FOLLOWING ITEMS. |
| |
| - FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| - FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| |
| |