Plan Review Notes For Permit 22061429 |
Permit Number |
22061429 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-07-05 13:43:52 | FIRE PROVISO: | | UPON COMPLETION THE AHJ WILL CONDUCT FIELD VERIFICATION | | THAT THE FACP WILL PASS A 24- HOUR BATTERY TEST AND IS | | PROPERLY REPORTING TO THE MONITORING SERVICE. NFPA 72 | | DUCT DETECTORS SHALL INITIATE A SUPERVISORY SIGNAL PER | | NFPA 72. 21.7 | | C. WALKER | | 561-804-4762 | | [email protected] | | |
|