Plan Review Notes For Permit 22061405 |
Permit Number |
22061405 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-07-08 05:44:23 | 1) THE CONDENSING UNITS MUST BE MOUNTED ON THE SAME | | PROPERTY AS THE BUILDING THEY SERVICE OR A DEEDED | | EASEMENT MUST BE SUBMITTED TO MR. RICHARD GATHRIGHT ABO | | FOR THE CITY OF WEST PALM BEACH. | | | | 2) THE CU-FOB CONCENSING UNIT WILL NEED TO BE PROTECTED | | FROM VEHICULAR TRAFFIC.FMC 303.4 | | | | 3) PROVIDE A DETAIL OF THE AHU-FOB ACCESS PANELS. FMC | | 306.1 | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | | | | | |
|