Plan Review Notes
Plan Review Notes For Permit 22061376
Permit Number 22061376
Review Stop B
Sequence Number 1
Notes
Date Text
2022-06-27 13:02:12JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL5680-R35 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-6 TO
 INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN
 BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE
 BOTTOM OF THE COVER PAGE. PRINT PAGES 1-6 ONLY.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL5680-R35 SELECTED SYSTEM NO. W-57 DO NOT
 MEET THE EXPOSURE CATEGORY C; ZONE 3 MINIMUM DESIGN
 PRESSURE REQUIREMENT OF -108.17. PLEASE SELECT SYSTEM
 NO. THAT MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE
 SIGNED AND SEALED ENGINEERED NAILING CALCULATION FOR
 ZONE 3. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  