2022-07-20 15:44:32 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22061363 |
| 7/20/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS 1.0A, 3.0P, & 3.1P: THE FLOOR PLAN INDICATES |
| A KITCHEN DISPLAY HOWEVER THE KITCHEN SINK AND |
| DISHWASHER ARE BEING DRAINED INTO THE SANITARY SYSTEM. |
| PLEASE NOTE IF THE KITCHEN WILL BE USED FOR COOKING AND |
| FOOD PREPARATION THEN A GREASE INTERCEPTOR WILL BE |
| REQUIRED- SEC. 1003.3.1 FBC P. PLEASE PROVIDE MORE |
| INFORMATION ON THE PLANS. |
| |
| 2) 3.1P: THE SCHEDULE SHOWS A RECIRCULATION PUMP BUT |
| THE RISER DOES NOT SHOW THE PUMP LOCATION OR THE HW |
| RETURN LINE- SEC. 607.2 FBC P. |
| |
| 3) 3.1P: A LIMITING DEVICE FOR CONTROLLING THE HOT |
| WATER TEMPERATURE AT THE KITCHEN SINK AND MOP SINK IS |
| REQUIRED PER SEC. 607.1.1 FBC P. PLEASE PROVIDE EITHER |
| A MASTER THERMOSTATIC MIXING VALVE OR POINT OF USE |
| DEVICES AT THE SINKS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |