Plan Review Notes For Permit 22061363 |
Permit Number |
22061363 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-06-29 11:13:02 | PLAN SET REFERENCES EXISTING SPRINKLER SYSTEM IN | | BUILDING. SYSTEM OCCUPANCY MUST BE | | "TIED INTO" EXISTING SYSTEMS TO PROVIDE FOR | | NOTIFICATION OF OCCUPANTS IN RESIDENTIAL OCCUPANCIES IN | | CASE OF SPRINKLER ACTIVATION. | | | | ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE | | BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING | | COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED, | | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU | | PRIOR TO ANY INSTALLATION. | | | | ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE | | COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND | | SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE | | REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE | | FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM. | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | INSPECTIONS AND APPROVAL. | | | | LT. BRIAN DOLAN | | DIVISION OF FIRE PREVENTION | | 561-804-4752 | | [email protected] | | |
|