2022-08-29 16:55:32FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 BREAKER TOO SMALL NEEDS TO BE AT LEAST A 50A BREAKER.
  
 625.41 OVERCURRENT PROTECTION.
  
 OVERCURRENT PROTECTION FOR FEEDERS AND BRANCH CIRCUITS
 SUPPLYING EQUIPMENT SHALL BE SIZED FOR CONTINUOUS DUTY
 AND SHALL HAVE A RATING OF NOT LESS THAN 125 PERCENT OF
 THE MAXIMUM LOAD OF THE EQUIPMENT. WHERE NONCONTINUOUS
 LOADS ARE SUPPLIED FROM THE SAME FEEDER, THE
 OVERCURRENT DEVICE SHALL HAVE A RATING OF NOT LESS THAN
 THE SUM OF THE NONCONTINUOUS LOADS PLUS 125 PERCENT OF
 THE CONTINUOUS LOADS.
  
  