2022-06-28 14:56:53THIS MUST COME IN AS A REVISION TO THE MASTER
 PERMIT-20081382 AND NOT A STAND ALONE MECHANICAL
 PERMIT.
 THE DESIGNER MUST PROVIDE DEMO DRAWINGS OF THE SHAFT
 AND THE DESIGN DRAWING SHOWING A CODE COMPLIANT SHAFT.
 THE MECHANICAL DESIGNER MUST PROVIDE A DEMO DRAWING OF
 THE ORIGINAL DESIGN OF THE DUCTWORK THAT IS INSIDE OF
 THE SHAFT. THIS SHOULD ALSO NAME THE DUCTWORK AND
 DETAIL THE USE OF THE DUCTWORK IN THE SHAFT.
 THE DESIGNER MUST ALSO SHOW A DRAWING WITH ALL OF THE
 DUCTWORK PUT BACK AS IT WAS ORIGINALLY AND IDENTIFYING
 EACH DUCT INSIDE THE SHAFT.
 THE UL SHAFT DETAIL SHOULD NOT BE ON THE MECHANICAL
 DRAWING AS THIS SHOULD BE ON THE BUILDING DRAWING AS
 THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE SHAFT.
  