2023-05-16 15:13:13------IT DOES NOT APPEAR THAT THESE COMMENTS WERE
 ADDRESSED - PLEASE RESPOND -----
  
 4TH PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. COMMENT NOT ADDRESSED - SHOW A WATER HEATER DETAIL
 FOR THE COMMERCIAL SPACE(S) THAT INCLUDES THE MIXING
 VALVE AT THE WATER HEATER.
 2020 FPC 607.1.1 - FOR THE COMMERCIAL SPACES, THERE
 SHALL BE A THERMOSTATIC MIXING VALVE (ASSE 1017) ON THE
 WATER HEATER TO REGULATE THE TEMPERATURE OF HOT WATER
 DELIVERY.
  
 2. COMMENT NOT ADDRESSED - SHOW A LAVATORY DETAIL THAT
 INCLUDES A 1070 MIXING DEVICE REQUIRED FOR PUBLIC
 HANDWASHING STATIONS - 2020 FPC 607.1.2/419.5 - ON THE
 LAVATORIES THAT ARE ACCESSIBLE TO THE PUBLIC, THERE
 SHALL BE A MIXING VALVE COMPLIANT WITH ASSE 1070 TO
 REGULATE THE TEMPERATURE OF TEMPERED WATER.
  
 3. DONE
  
 4. COMMENT NOT ADDRESSED -
 2017 WPB AMENDS 107.3.5.1.3 - THE REQUIRED RISER
 DIAGRAM IS NOT CODE COMPLIANT.
 A) CLOTHES WASHERS AND KITCHEN SINKS CANNOT BE INCLUDED
 IN WET VENTS OR OTHERWISE REQUIRED THEIR OWN INDIVIDUAL
 VENT. 2020 FPC 910.1 - 912.1
 B) TWO SHOWER FIXTURE DRAINS ARE CONNECTED TO THE SEWER
 WITHOUT A VENT 2020 FPC 901.2.1 (SWR SHOULD BE SHWR FOR
 SHOWER)
 C) VENTS SHALL BE VERTICAL UNTIL THEY ARE AT LEAST 6"
 ABOVE THE FLOOD RIM OF THE FIXTURE SERVED. 2020 FPC
 905.4
  
 5. DONE
  
 6. COMMENT NOT ADDRESSED -
 2020 FPC 403.1/403.3 - SHOW THE OCCUPANT LOAD OF THE
 RETAIL SPACES AND THE MINIMUM NUMBER OF FIXTURES
 REQUIRED FOR PUBLIC UTILIZATION FOR EACH SPACE OR
 ACCESS TO THE MINIMUM NUMBER OF FIXTURES REQIURED. A
 DRINKING FOUNTAIN AND/OR SERVICE SINK MAY BE REQUIRED.
  
 7. COMMENT NOT ADDRESSED -
 2017 WPB AMEND - 105.1/107.3 - IN CREATING A COMMERCIAL
 SPACE A BACKFLOW PERMIT IS REQUIRED.
  
 THE BUILDING SEWER CANNOT SERVE AS THE HORIZONTAL
 BUILDING DRAIN. SEVERAL FIXTURES APPEAR TO BE DIRECTLY
 CONNECTED TO THE SEWER WITHOUT VENT OR CLEANOUT. 2020
 FPC 301.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved