2023-07-21 09:50:56 | PETER E VALENTI |
| BUILDING/MECHANICAL PLANS EXAMINER II/INSPECTOR |
| [email protected] |
| 561 805 6673 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC M = FBC MECHANICAL |
| FBC FG = FBC FUEL GAS |
| |
| 5TH MECHANICAL REVIEW DENIED: |
| |
| |
| 1) PROVIDE HEAT LOAD CALCULATIONS FOR EACH UNIT FLORIDA |
| ENERGY COCE 2020 |
| |
| 2) PROVIDE ENERGY CALCULATIONS FOR EACH UNIT C402.1 |
| FLORIDA ENERGY CODE |
| 2020 |
| |
| 4) THE PLAN SHEET M-1 NEEDS TO BE REVISED AS THE |
| MINI-SPLIT LAYOUT IS NOT CLEAR: |
| A.) THE LABELING OF EACH OF THE AIR HANDLINGS UNIT & |
| CONDENSING UNITISS ARE THE SAME (AHU-1) & (CU-1). THESE |
| NEED TO BE LOCATION SPECIFIC TO EACH AIR HANDLING UNIT |
| AND EACH CONDENSING UNIT WITH THEIR OWN PLAN MARK. |
| B.) THE TONNAGE INFORMATION FOR EACH CONDENSING UNIT AS |
| INDICATED ON THE LAYOUT PLAN DOES NOT MATCH WITH THE |
| INFORMATION ON THE SCHEDULE OF UNITS. |
| C.) THE LINES ON THE LAYOUT SHEET THAT APPEAR TO |
| REPRESENT REFRIGERANT AND CONDENSATE LINES NEED TO BE |
| LABELED AND SOME OF THESE LINES ARE NOT CLEAR AS TO |
| THEIR DESTINATIONS SUCH AS THE LINES FOR #1004 COVERED |
| CONCRETE AREA. IT APPEARS THAT THE LINES FROM THE AHU |
| LOCATED AT THE GAME ROOM CONNECTS WITHTHE 2-TON |
| CONDENSING UNIT OUTSIDE OF #1004 BEDROOM #2 NOT THE |
| CONDENSING UNIT NEAR THE GAME ROOM. |
| D.) THE PLAN NEEDS TO SHOW THE LOCATION OF REFRIGERANT |
| AND CONDENSATE LINES (ABOVE CEILING, WITHIN SOFFITS, |
| BELOW SLAB ?) WITHIN THE INTERIOR OF STRUCTURES. |
| |