Date Text
2023-07-21 09:50:56PETER E VALENTI
 BUILDING/MECHANICAL PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 5TH MECHANICAL REVIEW DENIED:
  
  
 1) PROVIDE HEAT LOAD CALCULATIONS FOR EACH UNIT FLORIDA
 ENERGY COCE 2020
  
 2) PROVIDE ENERGY CALCULATIONS FOR EACH UNIT C402.1
 FLORIDA ENERGY CODE
 2020
  
 4) THE PLAN SHEET M-1 NEEDS TO BE REVISED AS THE
 MINI-SPLIT LAYOUT IS NOT CLEAR:
 A.) THE LABELING OF EACH OF THE AIR HANDLINGS UNIT &
 CONDENSING UNITISS ARE THE SAME (AHU-1) & (CU-1). THESE
 NEED TO BE LOCATION SPECIFIC TO EACH AIR HANDLING UNIT
 AND EACH CONDENSING UNIT WITH THEIR OWN PLAN MARK.
 B.) THE TONNAGE INFORMATION FOR EACH CONDENSING UNIT AS
 INDICATED ON THE LAYOUT PLAN DOES NOT MATCH WITH THE
 INFORMATION ON THE SCHEDULE OF UNITS.
 C.) THE LINES ON THE LAYOUT SHEET THAT APPEAR TO
 REPRESENT REFRIGERANT AND CONDENSATE LINES NEED TO BE
 LABELED AND SOME OF THESE LINES ARE NOT CLEAR AS TO
 THEIR DESTINATIONS SUCH AS THE LINES FOR #1004 COVERED
 CONCRETE AREA. IT APPEARS THAT THE LINES FROM THE AHU
 LOCATED AT THE GAME ROOM CONNECTS WITHTHE 2-TON
 CONDENSING UNIT OUTSIDE OF #1004 BEDROOM #2 NOT THE
 CONDENSING UNIT NEAR THE GAME ROOM.
 D.) THE PLAN NEEDS TO SHOW THE LOCATION OF REFRIGERANT
 AND CONDENSATE LINES (ABOVE CEILING, WITHIN SOFFITS,
 BELOW SLAB ?) WITHIN THE INTERIOR OF STRUCTURES.
  