Plan Review Notes For Permit 22061262 |
Permit Number |
22061262 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2023-06-06 10:53:13 | PLAN DENIED | | COMMENTS WERE NOT ANSWERED ON THE LAST THREE REVIEWS | | FOR MECHANICAL. | | 1) PROVIDE HEAT LOAD CALCULATIONS FOR EACH UNIT FLORIDA | | ENERGY COCE 2020 | | 2) PROVIDE ENERGY CALCULATIONS FOR EACH UNIT C402.1 | | FLORIDA ENERGY CODE | | 2020 | | 3) PROVIDE FRESH AIR CALCULATIONS FOR EACH UNIT 2020 | | FBC (M) 401 | | 4) THE PLAN SHOWS SOME UNITS HAVE NO AIR CONDITIONING | | AT ALL | | AND SOME UNITS HAVE THREE OR FOURA/C UNITS. SHOW WHERE | | THE AIR HANDLER | | AND CONDENSER GO FOR EACH UNIT. 107 FBC | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|