Plan Review Notes
Plan Review Notes For Permit 22061262
Permit Number 22061262
Review Stop B
Sequence Number 4
Notes
Date Text
2023-06-06 16:18:534TH REVIEW
 DATE: TUES. JUNE 06TH/ 2023
 ACTION: DENIED
 WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22061262
 ADD: 1911 N TAMARIND AVE
 CONT: BELACRIS CONSTRUCTION
 TEL: 305-244-0277
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1-9) COMPLIED.
 10A) COMPLIED.
  
 10B) SEMI-COMPLIED. THE FLOOR PLAN SHOWS 3 EGRESSES TO
 THE COMMERCIAL AREA ACCESSIBLE BY THE PUBLIC. AT LEAST
 ONE ENTRANCE NEEDS TO BE AN ACCESSIBLE ENTRANCE LEVEL
 WITH THE EXTERIOR OF THE BUILDING. 2020
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE. MISSING SIGNAGE AT THE
 DOORS NOT ACCESSIBLE INDICATING WHERE THE ACCESSIBLE
 ENTRANCE IS LOCATED.
  
  
 10C) COMPLIED.
  
 10D) COMPLIED.
  
 10E) COMPLIED.
  
 10F) 4TH REVIEW. FORMER REVIEW SHOWED A WORK LIVE LOFT.
 THIS REVIEW THE FLOOR PLAN A-2.0 SHOWS A LOUNGE, OFFICE
 KITCHENETTE AND A ROOM NOT SHOWING A USE WITH WHAT
 APPEARS TO BE A PRIVATE BATH, SHOWER, WATER CLOSET AND
 LAV. PLEASE PROVIDE WHAT THE USEAGE OF THE ROOM IN
 FRONT OF THIS BATHROOM? BATHROOM MAYBE REQUIRED TO BE
 ACCESSIBLE. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 10G) 4TH REVIEW. A-2. THE COVERSHEET SITE PLAN LIST
 BOTH ADDRESSES AS INTERIOR REMODEL RESIDENCE VERSES
 SHEET A-2.0 COMMERCIAL RETAIL SPACE, DISCREPANCY IN
 PLANS. 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 11) COMPLIED.
  
  
 12) 4TH REVIEW. SHEET S1.0 IS USING ASCE 7-05 IN THE
 2020 FBC-BUILDING WE ARE CURRENTLY USING THE ASCE 7-16.
 3RD REQUEST SHEETS A-3.0 & A-4.0 BOTH SHOW EXTERIOR
 ELEVATIONS AND NEW EXTERIOR OPENINGS, WINDOWS AND
 DOORS. THERE IS NO WIND DESIGN CRITERIA. 2020 FBC-B
 1603.1.4 WIND DESIGN CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 12.1) 4TH REVIEW. THE WIND PEED IS NO LONGER 135MPH.
 2020 FBC-BUILDING, VULT 170, VASD IS 132.
 .3RD REVIEW. ULTIMATE DESIGN WIND SPEED, VULT,
 (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 12.2. RISK CATEGORY. SHEET S1 THE RISK CATEGORY IS
 LISTED AS III, THIS IS FOR POLICE STATIONS, FIRE
 STATIONS & HOSPITALS. THIS BUILDING IS A RISK CATEGORY
 II. WITH LOWER ASSOCIATED PRESSURES. IMPORTANCE FACTOR
 IS NOT 1.15 THAT AGAIN IS FOR FOR POLICE STATIONS, FIRE
 STATIONS & HOSPITALS. THE IMPORTANCE FACTOR IS 1.0.
  
 12.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 12.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 12.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 12.6.4TH REQUEST. PLEASE UPDATE PRESSURES FOR ZONES
 1-5. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 13) . 4TH D REQUEST. PLEASE SUBMIT THE COMPONENTS AND
 CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS
  
 14) 4TH REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 15A) 4TH REQUEST. NOT ADDRESSED. SHEET A-3.0 ELEVATIONS
 SHOWS THE NORTH ELEVATION TO THE LEFT OF THE BUILDING
 PEOPLE ARE WALKING ON THE PUBLIC SIDEWALK ELEVATION 0
 INCHES-0 FEET. THE NEW DOORS IN THE EXISTING OPENINGS
 SHOW A DOOR STOOP APPROXIMATELY 4 INCHES IN HEIGHT NONE
 OF THE DOORWAYS INTO ANY OF THE OFFICES OR LIVE/ WORK
 LOFT ARE ACCESSIBLE. GOOGLE MAPS SHOW THE DOORWAYS
 ELEVATED APPROXIMATELY 4 INCHES ABOVE THE SIDEWALK.
 2020 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION). 2020 FBC-ACCESS. CODE
 CHANGES IN LEVEL 303.2 AND 303.3. WHERE CHANGES IN
 LEVEL ARE PERMITTED IN THE FLOOR OR GROUND SURFACES,
 THEY SHALL COMPLY WITH SECTION 303. SEE 303.1 & 303.2.
  
 15B) 4TH REVIEW. NO DOOR SCHEDULE. 2020 ACCESS. CODE
 404.2.3. CLEAR WIDTH & SIZE OF DOORS, 2020 FBC-B
 1010.1.1. WHERE THIS SECTION REQUIRES A MINIMUM CLEAR
 WIDTH OF 32- INCHES OR A 34-INCH DOOR MINIMUM. THE
 MINIMUM SIZE OF A SWING DOORS IS MEASURED CLEAR OPENING
 OF THE DOORWAY WITH THE SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 15C) COMPLIED.
  
 16) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  