2023-06-06 16:18:53 | 4TH REVIEW |
| DATE: TUES. JUNE 06TH/ 2023 |
| ACTION: DENIED |
| WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22061262 |
| ADD: 1911 N TAMARIND AVE |
| CONT: BELACRIS CONSTRUCTION |
| TEL: 305-244-0277 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1-9) COMPLIED. |
| 10A) COMPLIED. |
| |
| 10B) SEMI-COMPLIED. THE FLOOR PLAN SHOWS 3 EGRESSES TO |
| THE COMMERCIAL AREA ACCESSIBLE BY THE PUBLIC. AT LEAST |
| ONE ENTRANCE NEEDS TO BE AN ACCESSIBLE ENTRANCE LEVEL |
| WITH THE EXTERIOR OF THE BUILDING. 2020 |
| FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| INTERNATIONAL BUILDING CODE. MISSING SIGNAGE AT THE |
| DOORS NOT ACCESSIBLE INDICATING WHERE THE ACCESSIBLE |
| ENTRANCE IS LOCATED. |
| |
| |
| 10C) COMPLIED. |
| |
| 10D) COMPLIED. |
| |
| 10E) COMPLIED. |
| |
| 10F) 4TH REVIEW. FORMER REVIEW SHOWED A WORK LIVE LOFT. |
| THIS REVIEW THE FLOOR PLAN A-2.0 SHOWS A LOUNGE, OFFICE |
| KITCHENETTE AND A ROOM NOT SHOWING A USE WITH WHAT |
| APPEARS TO BE A PRIVATE BATH, SHOWER, WATER CLOSET AND |
| LAV. PLEASE PROVIDE WHAT THE USEAGE OF THE ROOM IN |
| FRONT OF THIS BATHROOM? BATHROOM MAYBE REQUIRED TO BE |
| ACCESSIBLE. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. |
| |
| 10G) 4TH REVIEW. A-2. THE COVERSHEET SITE PLAN LIST |
| BOTH ADDRESSES AS INTERIOR REMODEL RESIDENCE VERSES |
| SHEET A-2.0 COMMERCIAL RETAIL SPACE, DISCREPANCY IN |
| PLANS. 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 11) COMPLIED. |
| |
| |
| 12) 4TH REVIEW. SHEET S1.0 IS USING ASCE 7-05 IN THE |
| 2020 FBC-BUILDING WE ARE CURRENTLY USING THE ASCE 7-16. |
| 3RD REQUEST SHEETS A-3.0 & A-4.0 BOTH SHOW EXTERIOR |
| ELEVATIONS AND NEW EXTERIOR OPENINGS, WINDOWS AND |
| DOORS. THERE IS NO WIND DESIGN CRITERIA. 2020 FBC-B |
| 1603.1.4 WIND DESIGN CRITERIA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 12.1) 4TH REVIEW. THE WIND PEED IS NO LONGER 135MPH. |
| 2020 FBC-BUILDING, VULT 170, VASD IS 132. |
| .3RD REVIEW. ULTIMATE DESIGN WIND SPEED, VULT, |
| (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND |
| SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 12.2. RISK CATEGORY. SHEET S1 THE RISK CATEGORY IS |
| LISTED AS III, THIS IS FOR POLICE STATIONS, FIRE |
| STATIONS & HOSPITALS. THIS BUILDING IS A RISK CATEGORY |
| II. WITH LOWER ASSOCIATED PRESSURES. IMPORTANCE FACTOR |
| IS NOT 1.15 THAT AGAIN IS FOR FOR POLICE STATIONS, FIRE |
| STATIONS & HOSPITALS. THE IMPORTANCE FACTOR IS 1.0. |
| |
| 12.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. |
| |
| 12.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 12.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 12.6.4TH REQUEST. PLEASE UPDATE PRESSURES FOR ZONES |
| 1-5. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| CONVERSION VULT TO VASD. |
| |
| 13) . 4TH D REQUEST. PLEASE SUBMIT THE COMPONENTS AND |
| CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS |
| (B) WINDOWS |
| |
| 14) 4TH REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 15A) 4TH REQUEST. NOT ADDRESSED. SHEET A-3.0 ELEVATIONS |
| SHOWS THE NORTH ELEVATION TO THE LEFT OF THE BUILDING |
| PEOPLE ARE WALKING ON THE PUBLIC SIDEWALK ELEVATION 0 |
| INCHES-0 FEET. THE NEW DOORS IN THE EXISTING OPENINGS |
| SHOW A DOOR STOOP APPROXIMATELY 4 INCHES IN HEIGHT NONE |
| OF THE DOORWAYS INTO ANY OF THE OFFICES OR LIVE/ WORK |
| LOFT ARE ACCESSIBLE. GOOGLE MAPS SHOW THE DOORWAYS |
| ELEVATED APPROXIMATELY 4 INCHES ABOVE THE SIDEWALK. |
| 2020 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| BUILDING CODE (2003 EDITION). 2020 FBC-ACCESS. CODE |
| CHANGES IN LEVEL 303.2 AND 303.3. WHERE CHANGES IN |
| LEVEL ARE PERMITTED IN THE FLOOR OR GROUND SURFACES, |
| THEY SHALL COMPLY WITH SECTION 303. SEE 303.1 & 303.2. |
| |
| 15B) 4TH REVIEW. NO DOOR SCHEDULE. 2020 ACCESS. CODE |
| 404.2.3. CLEAR WIDTH & SIZE OF DOORS, 2020 FBC-B |
| 1010.1.1. WHERE THIS SECTION REQUIRES A MINIMUM CLEAR |
| WIDTH OF 32- INCHES OR A 34-INCH DOOR MINIMUM. THE |
| MINIMUM SIZE OF A SWING DOORS IS MEASURED CLEAR OPENING |
| OF THE DOORWAY WITH THE SWINGING DOORS SHALL BE |
| MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| WITH THE DOOR OPEN 90 DEGREES. |
| |
| 15C) COMPLIED. |
| |
| 16) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |