Plan Review Notes
Plan Review Notes For Permit 22061262
Permit Number 22061262
Review Stop B
Sequence Number 1
Notes
Date Text
2022-11-14 13:26:09WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22061262
 ADD: 1911 N TAMARIND AVE
 CONT: BELACRIS CONSTRUCTION
 TEL: 305-244-0277
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 14TH/ 2022
 ACTION: DENIED
  
 1) PLEASE ADDRESS THE ADDRESSING CONCERNS BEING THIS
 PROPERTY IS A CORNER PROPERTY WITH MULTIPLE PROPOSED
 TENANTS AND USES. 2020 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED
 2) PLEASE REVIEW THE SUBMITTED (UPLOADED) PLAN AND
 LABELING. EXAMPLE THE UPLOADED LIFE SAFETY PLAN IS
 ACTUALLY THE M1-0 PLAN. THE E-1.0 IS ACTUALLY
 ELEVATIONS. . A-3.0 IS LABELED THE ELEVATIONS BUT IS
 ACTUALLY E-1.0, ETC???
 DISCREPANCY IN PLANS. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED.
  
 3) THERE IS NO EXISTING FLOOR PLAN SHEET A-2.0 SHOWS
 THE PROPOSED FLOOR PLAN WITH THE PROPOSED BEDROOMS 3 &
 4 WHAT WERE THESE AREAS PREVIOUSLY USED AS? WITH THE
 NEW PROPOSED USE, THE PROPERTY LINE IS LISTED AS 2FEET
 2 INCHES. THE 2020 FBC-BUILDING CODE TABLE 602
 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS
 BASED ON DISTANCE & TABLE 705.8 MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION. THIS SAME
 WALL THE SURVEY SHOWS APPROXIMATELY 9 FEET FROM THE
 PROPERTY LINE, WHY THE DISCREPANCY?
  
 4) SHEET A-2.0 SHOWS ON THE BACK OF THE BUILDING NINE
 FEET EIGHT INCHES TO THE PROPERTY LINE WHEREAS THE
 SURVEY INDICATES 5.4 FEET AND 5.2 FEET. THE 2020
 FBC-BUILDING CODE TABLE 602 FIRE-RESISTANCE RATING
 REQUIREMENTS FOR EXTERIOR WALLS BASED ON DISTANCE &
 TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS
 BASED ON FIRE SEPARATION DISTANCE AND DEGREE OF OPENING
 PROTECTION. THIS SAME WALL THE SURVEY SHOWS
 APPROXIMATELY 9 FEET FROM THE PROPERTY LINE, WHY THE
 DISCREPANCY?
  
 5) SHEET A-2.0 PLEASE SHOW FOR THE PROPOSED BEDROOM
 NUMBER THREE THE NEW LOCATION FOR THE EGRESS WINDOW IN
 ACCORDANCE WITH 2020 FBC-BUILDING CODE 1030.2 & 1030.3.
  
 6A) SHEET A-2.0 PLEASE PROVIDE OCCUPANCY CLASSIFICATION
 FOR THE PROPOSED 4 BEDROOM AND STUDIO APARTMENT? 2020
 FBC-BUILDING CODE 310.4 R-2, 310.5 R-3 OR 310.6 R-4.
  
 6B) DEPENDING ON OCCUPANCY TYPE THERE MAYBE
 REQUIREMENTS FOR ACCESSIBILITY. ADDITIONAL INFORMATION
 IS REQUIRED. 107.2.1.
  
 7A) SHEET A-2.0 THE PROPOSED 4 BEDROOM NOR THE PROPOSED
 STUDIO APARTMENT SHOW COMPLIANCE WITH SECTION 420.4
 SEPARATION WALLS AND THE REQUIREMENTS FOUND IN 708.4.
 7B) PROVIDE THE UL OR GYPSUM ASSOCIATION LISTING NUMBER
 FOR THE FIRE PARTITION SEE 708.3 FIRE RESISTANCE
 RATING.
  
 8A) SHEET A-2.0 FLOOR PLAN THE EXISTING FRONT PORCH AT
 4-BEDROOM UNIT INDICATES NEW GWB (GYPSUM WALL BOARD)
 BUILDOUT OVER EXISTING STRUCTURAL COLUMN. GYPSUM WALL
 BOARD IS USED FOR INTERIOR WALLS AND CEILINGS. GYPSUM
 SHEATHING IS FOR EXTERIOR USE WITH A STUCCO OR SIMILAR
 FINISH PRODUCT. PLEASE ALSO PROVIDE THE FRAMING SINCE
 THIS IS AN EXTERIOR ELEMENT, 170 VULT WIND SPEED.
  
 8B) PROVIDE COMPLIANCE WITH FBC-BUILDING SECTION 420.6
 FIRE & SMOKE ALARMS.
  
 9) SHEET A-2.0 DETAIL # 4 & 5 SHOW A WALL SECTION BUT
 THE SECTION INDICATES #5 REBAR DOWELED INTO THE
 FOUNDATION, THIS SECTION DOES NOT PROVIDE A BEAM AT THE
 TOP TO DOWEL INTO OR IF A NEW BEAM IS TO BE REQUIRED,
 PART OF THE MAIN WIND FORCE RESISTING SYSTEM (MWFRS).
 THE SAME HOLDS TRUE WITH WALL DETAIL # 5. 107.2.1.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) SHEET A-2.0 WHAT APPEARS TO BE A LIVE/ WORK UNIT
 THAT WILL NEED SHOW COMPLIANCE WITH THE 2020
 FBC-BUILDING CODE SECTION 419.
  
 10A) SHOW AREA LIMITATIONS IN ACCORDANCE WITH 419.1.1
 LIMITATIONS.
  
 10B) THE FLOOR PLAN SHOWS 2 EGRESSES TO THE COMMERCIAL
 AREA ACCESSIBLE BY THE PUBLIC. AT LEAST ONE ENTRANCE
 NEEDS TO BE A ACCESSIBLE ENTRANCE LEVEL WITH THE
 EXTERIOR OF THE BUILDING. 2020 FBC-ACCESSIBILITY CODE
 SECTION 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000
 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 NEW BUILDINGS ONLY, SEE EXCEPTIONS IN EXISTING
 BUILDINGS.
  
 10C) THE FLOOR PLAN SHOWS A POWDER ROOM WITH A LAV AND
 WATER CLOSET, DOES NOT MEET SECTION CLEARANCES AT WATER
 CLOSETS. 604.3 CLEARANCE. CLEARANCES AROUND THE WATER
 CLOSETS AND IN TOILET COMPARTMENTS SHALL COMPLY WITH
 604.3.
 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR
 WALL.
  
 10D) PLEASE PROVIDE WALL ELEVATIONS FOR THE POWDER ROOM
 FOR ALL OF THE GRAB BAR REQUIREMENTS, PAPER HOLDER, LAV
 AND MIRROR. SEE CHAPTER 6 OF THE 2020 ACCESSIBILITY
 CODE.
  
 10E) 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE. 1210.2.2 WALLS &
 PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS, AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL
 USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT
 ADVERSELY AFFECTED BY MOISTURE.
  
 10F) THE FLOOR PLAN FOR THE LIVE/ WORK UNIT NEEDS TO
 SHOW COMPLIANCE WITH 420 FIRE & SMOKE ALARMS.
  
 10G) SHEET A-2.0 THE LIVE/ WORK UNIT BEDROOM # 2 DOES
 NOT HAVE AT LEAST ONE EMERGENCY ESCAPE AND RESCUE
 OPENING, 2020 FBC-BUILDING SECTION 1030.1 & 1030.2.
  
 11) ARIEL VIEW OF THE PROPERTY SHOWS IN THE MIDDLE OF
 THE LIVE WORK UNIT WHAT APPEARS A BEARING WALL ABOVE
 THE ROOF LINE PARALLEL WITH STATE ST. THERE IS NO
 MENTION OF WHERE THIS WALL IS IN THE FLOOR PLAN,
 ALREADY REMODELED? 107.2.1. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 12) SHEETS A-3.0 & A-4.0 BOTH SHOW EXTERIOR ELEVATIONS
 AND NEW EXTERIOR OPENINGS, WINDOWS AND DOORS. THERE IS
 NO WIND DESIGN CRITERIA. 2020 FBC-B 1603.1.4 WIND
 DESIGN CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 12.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 12.2. RISK CATEGORY.
  
 12.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 12.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 12.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 12.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 13) . PLEASE SUBMIT THE COMPONENTS AND CLADDING PRODUCT
 APPROVALS. 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS
  
 14) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 15) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  