Plan Review Notes
Plan Review Notes For Permit 22061253
Permit Number 22061253
Review Stop E
Sequence Number 2
Notes
Date Text
2022-10-03 11:09:50ELECTRIC REVIEW FAILED
 1) RISER DIAGRAM AND LOAD CALCULATION DETAIL
 CONFLICTING SIZED SERVICE. PLEASE CORRECT AS APPLICABLE
 NEC 215.5
 2) ELECTRIC FLOOR PLAN DETAILS 2 ELECTRIC PANELS
 CONFLICTING WITH RISER DIAGRAM. PLEASE CORRECT A S
 APPLICABLE. FBC 107.2
 3) LOAD CALCULATION DOES NOT INCLUDE ALL LOADS AS
 REQUIRED. MISSING DOUBLE OVEN LOAD AND SECOND AIR
 HANDLER AND CONDENSOR. ENSURE ALL ELECTRIC LOADS ARE
 INCLUDED. PLEASE CORRECT AS APPLICABLE. NEC 215.5 AND
 220.40 OR 220.80
 4) ELECTRIC FLOOR PLAN DOES NOT DETAIL THE ADDITIONAL
 AIR CONDITIONING EQUIPMENT. PLEASE CORRECT AS
 APPLICABLE. FBC 107.2
 5) SEE SIGNATURE REVIEW
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  