Plan Review Notes For Permit 22061231 |
Permit Number |
22061231 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-07-18 08:52:45 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) VALUE OF WORK ON PERMIT IS LOW, PLEASE SUBMIT A COST | | BREAKDOWN OF THE VALUE OF THE LABOR AND MATERIALS FOR | | THIS PROJECT (38K) | | | | 2) LOAD SIDE TAP FOR SYSTEM DOES NOT MEET THE | | REQUIREMENTS OF 705.12 (B) 150+56= 206 BUSS IS RATED AT | | 200 PER PLANS. | | | | 3) PLANS WILL NEED A DIGITAL SIGNATURE VERFIABLE BY A | | THIRD PARTY, THESE PLANS ARE A COPY. |
|