2022-08-31 10:23:43RESIDENTIAL(R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061225
 4098 WINNIPEG WAY
  
 1- SIZE OF ANCHOR SPECIFIED (ITW TAPCON 1/4X2-1/4) FOR
 CONCRETE INSTALLATION DOESN'T PROVIDE 1.75 INCH
 EMBEDMENT INTO THE CONCRETE AS REQUIRED BY ANCHOR
 SCHEDULE TABLE ON SHEET 12 OF 18 OF SHUTTERS DRAWINGS
 SUBMITTED. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- BASED ON THE SHUTTERS SPAN. THE ANCHOR SPACING
 SPECIFIED AT THE BOTTOM FOR OPENINGS #1, #2, #4 AND #9
 IS INCORRECT. SEE THE SHUTTERS SPACING ON THE ANCHOR
 SPACING TABLE ON SHEET 13 OF 18 OF SHUTTERS DRAWINGS
 SUBMITTED. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- TYPE OF ANCHOR SPECIFIED UNDER THE BUILDING HEIGHT
 IS INCOMPLETE. ITW IS JUST THE BRAND NAME. NEED TO
 PROVIDE COMPLETE SPECIFICATIONS OF ANCHORS TO BE
 INSTALLED. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- INFORMATION ENTERED IN COLUMN #4 FOR OPENING #3 IS
 INCORRECT. THERE IS NOT ANCHOR TYPE B2. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: THIS COLUMN IS TO SPECIFY THE SHUTTER MOUNTING
 CONDITION. FOR EXAMPLE WALL MOUNT SECTION C AS SHOWN ON
 SHEET 04 OF 18, BUILT OUT MOUNTING, ETC. ANCHOR TYPE A,
 A1, ETC. SHOULD BE ENTERED IN THE SPECIFIC ANCHOR TYPE
 COLUMN.
  
 5- INSTALLATION SCHEDULE IS MISSING THE INFORMATION IN
 THE SUBSTRATE COLUMN (CONCRETE OR CONCRETE BLOCK,
 ETC.).
 SEC. 107.2.1 CITY AMENDMENTS.
  
 6- ACCORDING SHUTTERS ARE INSTALLED VERTICALLY NOT
 HORIZONTALLY. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved