Plan Review Notes
Plan Review Notes For Permit 22061221
Permit Number 22061221
Review Stop Z
Sequence Number 2
Notes
Date Text
2022-11-03 08:55:08** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SHOW SETBACK DIMENSION FROM THE JUNCTION BOX TO THE
 PROPERTY LINE. PLEASE NOTE THAT MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FT. INTO A REQUIRED
 SETBACK. [ZLDR S.94-305(B)(4)]
  
 [9/16/22 REPEAT COMMENT: NOT ADDRESSED. NOT SETBACK
 DIMENSIONS HAVE BEEN PROVIDED IN THE PLANS TO
 DEMONSTRATE COMPLIANCE WITH THE ZLDRS.]
  
  
 2.) THE REVISED PHOTOMETRIC PLAN DOES NOT SHOW THE
 PHOTOMETRIC SPILLOVER BEYOND THE PROPERTY LINES TO SHOW
 THAT THE ILLUMINATION WILL NOT EXCEED 1-FOOT CANDLE
 BEYOND THE PROPERTY LINE. [ZLDR S.94-207]
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * MASTER PERMIT #21110846 (LIGHT POLE FIXTURES ONLY)
  
 * ZONE: GC
  