Plan Review Notes For Permit 22061221 |
Permit Number |
22061221 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-09-16 11:12:43 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) SHOW SETBACK DIMENSION FROM THE JUNCTION BOX TO THE | | PROPERTY LINE. PLEASE NOTE THAT MECHANICAL EQUIPMENT | | MAY NOT PROJECT MORE THAN 4 FT. INTO A REQUIRED | | SETBACK. [ZLDR S.94-305(B)(4)] | | | | | | NOTES: | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | QUESTIONS. | | | | * MASTER PERMIT #21110846 (LIGHT POLE FIXTURES ONLY) | | | | * ZONE: GC | | |
|