Plan Review Notes For Permit 22061092 |
Permit Number |
22061092 |
|
Review Stop |
B |
Sequence Number |
9 |
|
Notes |
Date |
Text |
2023-06-26 14:24:18 | REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A-201 HAS A STATEMENT THAT A 90 MIN. FIRE | | RATED DOOR IS REQUIRED - PLEASE SHOW THE LOCATION OF | | THIS 90 MIN. FIRE RATED DOOR. | | | | 2) DOOR D8 SHOULD BE FIRE RATED - FBC TABLE 716.5 - | | BASED ON THE EXTERIOR WALL RATING FBC TABLE 705.8 | | | | 3) DOOR SCHEDULE NEEDS TO SHOW THE DOOR FIRE RATINGS - | | FBC TABLE 716.5 | | | | 4) PLEASE SHOW THE FIRE RATED DOORS TO BE SELF CLOSING | | - FBC 716.5.9 | | | | 5) PLEASE SHOW THE ACCESSIBLE SEATING AREA FOR THE | | TABLES AND BAR ON THE GROUND FLOOR REMODEL (309) - FBC | | A 226.2 | | | | 6) PLEASE SHOW THE ACCESSIBLE POOL ENTRY - FBC A 242.2 | | | | | | | | | | | | | | | | |
|