Plan Review Notes
Plan Review Notes For Permit 22061092
Permit Number 22061092
Review Stop B
Sequence Number 9
Notes
Date Text
2023-06-26 14:24:18REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A-201 HAS A STATEMENT THAT A 90 MIN. FIRE
 RATED DOOR IS REQUIRED - PLEASE SHOW THE LOCATION OF
 THIS 90 MIN. FIRE RATED DOOR.
  
 2) DOOR D8 SHOULD BE FIRE RATED - FBC TABLE 716.5 -
 BASED ON THE EXTERIOR WALL RATING FBC TABLE 705.8
  
 3) DOOR SCHEDULE NEEDS TO SHOW THE DOOR FIRE RATINGS -
 FBC TABLE 716.5
  
 4) PLEASE SHOW THE FIRE RATED DOORS TO BE SELF CLOSING
 - FBC 716.5.9
  
 5) PLEASE SHOW THE ACCESSIBLE SEATING AREA FOR THE
 TABLES AND BAR ON THE GROUND FLOOR REMODEL (309) - FBC
 A 226.2
  
 6) PLEASE SHOW THE ACCESSIBLE POOL ENTRY - FBC A 242.2
  
  
  
  
  
  
  
  