Plan Review Notes For Permit 22061092 |
Permit Number |
22061092 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2023-01-20 13:30:01 | ADDITION AND REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A201 AND A101 THE FLOOR PLAN SHOULD MATCH | | (VESTIBULE WALL CHANGES). FBC WPB 107 | | | | 2) THE SIGNED AND SEALED STRUCTURAL DRAWINGS AND THE | | SIGNED AND SEALED THRESHOLD INSPECTOR FORM DO NOT SHOW | | AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED | | DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). | | | | 3) NEW DOORS AT THE FRONT OF THE BUILDING SHOULD NOT | | ENCROACH IN TO THE PUBLIC RIGHT OF WAY FBC 3202.2 | | ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN HEIGHT. | | DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE | | PUBLIC RIGHT-OF-WAY. | | | | 4) BUILDING IS A RISK CATEGORY III - WIND DESIGN NEEDS | | TO BE BASED ON 180 MPH PER FBC WPB SECTION 120 | | | | | | |
|