Plan Review Notes
Plan Review Notes For Permit 22061092
Permit Number 22061092
Review Stop M
Sequence Number 3
Notes
Date Text
2022-11-30 09:22:053RD REVIEW FMC
 PERMIT: 22061092
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE COMMENTS BELOW FOR THE KITCHEN HOOD EXHAUST IS ONLY
 HERE BECAUSE THEY ARE MINGLED WITH THE DESIGN OF THIS
 BUILDING, IF I WAITED UNTIL THE KITCHEN HOOD PERMITS
 AND REVIEW IT COULD MEAN A LOT OF CHANGES. NOTE THAT
 THIS IS NOT A REVIEW OF THE KITCHEN HOODS AND GREASE
 DUCT. JUST REFERENCE FOR THE CONSTRUCTION OF THIS
 REMODEL.
  
 1) I DO NOT SEE THE NOTE ON THE MECHANICAL DRAWINGS
 THAT STATES THE KITCHEN HOOD AND GREASE DUCT WILL
 REQUIRE A SEPARATE PERMIT APPLICATION AND SUBMITTAL FOR
 PLAN REVIEW AS THEY WILL NOT BE REVIEWED UNDER THIS
 PERMIT. PLEASE ADD THE NOTE TO THE MECHANICAL DRAWINGS.
  
 2) I DO NOT SEE THE NOTE ON THE MECHANICAL DRAWINGS
 THAT STATES THE REFRIGERATION FOR THE WALK-IN COOLERS
 AND FREEZER WILL REQUIRE A SEPARATE PERMIT APPLICATION
 AND SUBMITTAL FOR PLAN REVIEW AS THEY WILL NOT BE
 REVIEWED UNDER THIS PERMIT. PLEASE ADD THE NOTE TO THE
 MECHANICAL DRAWINGS.
  
 3) SHEET M-102: THE HOOD EXHAUST TERMINATION LOCATION
 MUST BE A MINIMUM OF 10 FEET FROM THE PROPERTY LINE.
 FMC 501.3.1 ITEM NUMBER 2
  
 4) THE WOMEN???S BATH ROOMS ON THE 1ST FLOOR SHOWS AN
 EXHAUST GRILLE IN THE HANDICAP BOOTH WITH 0 CFM???S OF
 EXHAUST. PLEASE CORRECT THIS. FBC 107.3.5
  
 5) THE DIGITAL SIGNATURE ON THE MECHANICAL DRAWINGS ARE
 COPIES OF THE ORIGINAL AS THEY DO NOT SHOW AS DIGITAL
 SIGNATURES IN OUR SOFTWARE. PLEASE PROVIDE THE ORIGINAL
 DIGITALLY SIGNED DRAWINGS. FS 471/481
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  