Plan Review Notes For Permit 22061092 |
Permit Number |
22061092 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2022-12-05 13:50:09 | ADDITION AND REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A201 SHOWS EXTERIOR WALL OPENING | | CALCULATIONS - THE REAR WALL WHICH IS 9' 8" FROM THE | | CENTER OF THE ALLEY HAS A DOOR OPENING WHICH IS NOT | | SHOWN ON THE OPENING CALCULATIONS. - FBC TABLE 705.8 | | | | 2) THE SIGNED AND SEALED STRUCTURAL DRAWINGS AND THE | | SIGNED AND SEALED THRESHOLD INSPECTOR FORM DO NOT SHOW | | AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED | | DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). | | | | 3) NEW DOORS AT THE FRONT OF THE BUILDING SHOULD NOT | | ENCROACH IN TO THE PUBLIC RIGHT OF WAY FBC 3202.2 - | | PLEASE PROVIDE A SURVEY | | | | 4) CANNOT HAVE AN ELEVATOR IN A STAIR EXIT VESTIBULE - | | FBC 1028.1 EXCEPTION 2 - 2.4.THE AREA IS USED ONLY FOR | | MEANS OF EGRESS AND EXITS DIRECTLY TO THE OUTSIDE. | | | | 5) BUILDING IS A RISK CATEGORY III - WIND DESIGN NEEDS | | TO BE BASED ON 180 MPH PER FBC WPB SECTION 120 | | | | | | |
|