2022-09-26 12:40:28 | 1ST PLUMBING REVIEW |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. ---NOT ADDRESSED----2020 FPC 1003.3.1 - ONLY DEVICES |
| DESIGNED TO RECEIVE FATS, OILS AND GREASE SHALL BE |
| DIRECTED TO THE GREASE WASTE. PLEASE SHOW THAT THE ICE |
| BINS AND HANDS SINK GO TO THE SANITARY AND NOT THE |
| GREASE WASTE. |
| |
| 2. ---NOT ADDRESSED----2017 WPB AMEND - 107.3 - THE |
| GREASE INTERCEPTOR REQUIRES A SEPARATE PERMIT AND NEEDS |
| TO BE APPLIED FOR BEFORE THE RELEASE OF THE MASTER |
| PERMIT. |
| |
| 3. ---NOT ADDRESSED----2020 FPC 905.4 - ON EACH END OF |
| THE BATHROOMS, THE VENT NEAR THE WATER CLOSET IS |
| HORIZONTAL AND CANNOT BE UNTIL IT IS 6" ABOVE THE FLOOD |
| RIM OF THE FIXTURES SERVED. |
| |
| 4. ---NOT ADDRESSED----2020 FPC 905.4 - THE VENTS FOR |
| THE GREASE INTERCEPTORS ARE HORIZONTAL WHILE DRY AND |
| CANNOT BE. THE VENT CANNOT BE A HORIZONTAL DRY VENT |
| UNTIL IT IS 6" ABOVE THE FLOOD RIM OF THE FIXTURES |
| SERVED. |
| 5. DONE |
| |
| 6. ---NOT ADDRESSED----WPB ORD. SEC. 90 - 126 - THE |
| DISCHARGE FROM AIR HANDLERS/AIR CONDITIONING CONDENSATE |
| CANNOT DISCHARGE INTO THE SANITARY. IT MUST GO TO THE |
| STORM OR OTHER APPROVED PLACE OF DISPOSAL. |
| |
| 7. ---NOT ADDRESSED----2020 FPC 419.5/607.1.2 - PLEASE |
| INCLUDE A DETAIL SHOWING COMPLIANCE WITH THE |
| REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING |
| STATIONS THAT INCLUDES THE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070. |
| |
| |
| |
| |
| ---NOT ADDRESSED----WHEN RESUBMITTING, IT IS HELPFUL TO |
| PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |
| OFFICE: 561-805-6692 |
| CELL: 561-517-4293 |
| EMAIL: [email protected] |
| |