2022-10-20 15:32:28 | FLORIDA BUILDING CODE 2020 7TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| NFPA 70 2017 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 1) PAGE 103, 302 WEATHER PROOF OUTLETS IN WET LOCATION |
| REQUIRE A WEATHER PROOF INUSE COVE COVER |
| |
| 46.9 0(1) RECEPTACLES OF 15 AND 20 AMPERES IN A WET |
| LOCATION. |
| |
| RECEPTACLES OF 15 AND 20 AMPERES, 125 AND 250 VOLTS |
| INSTALLED IN A WET LOCATION SHALL HAVE AN ENCLOSURE |
| THAT IS WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG |
| CAP IS INSERTED. AN OUTLET BOX HOOD INSTALLED FOR |
| THIS PURPOSE SHALL BE LISTED AND SHALL BE IDENTIFIED AS |
| ???EXTRA-DUTY.??? OTHER LISTED PRODUCTS, ENCLOSURES, OR |
| ASSEMBLIES PROVIDING WEATHERPROOF PROTECTION THAT DO |
| NOT UTILIZE AN OUTLET BOX HOOD NEED NOT BE MARKED |
| ???EXTRA DUTY.??? |
| |
| PLEASE SUBMIT A LISTING FOR THE INUSE FLOOR BOX COVER. |
| |
| 2) RISER IS MISSING PLEASE SUBMIT A RISER DIAGRAM 215.5 |
| |
| 3) PANEL SCHEDULES ARE MISSING. |
| |
| 4) GFCI REQUIREMENTS HAVE BEEN EXPANDED IN THE 2017 NEC |
| PLEASE READ 210.8(B) FOR TYPE AND LOCATION OF GFCIS. |
| |
| 210.8(B) OTHER THAN DWELLING UNITS. |
| |
| ALL SINGLE-PHASE RECEPTACLES RATED 150 VOLTS TO GROUND |
| OR LESS, 50 AMPERES OR LESS AND THREE-PHASE RECEPTACLES |
| RATED 150 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS |
| INSTALLED IN THE FOLLOWING LOCATIONS SHALL HAVE |
| GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |