2022-10-07 08:57:28 | ADDITION AND REMODEL |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS |
| AND ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE |
| REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| OF RECORD FBC WPB 107.3.4 |
| |
| 2) PLEASE SHOW ON THE DRAWINGS THAT TERMITE TREATMENT |
| IS A REQUIREMENT PER FBC 1816 |
| |
| 3) PLEASE SHOW WALL DESIGNATIONS ON THE FLOOR PLANS - |
| SHOW FIRE WALLS ETC. FBC WPB 107.2 |
| |
| 4) BASED ON THE DISTANCE FROM THE CENTER OF THE ALLY |
| (SHOW THE DISTANCE) TO THE REAR WALL. THE REAR WALL |
| NEEDS TO SHOW AS 1 HOUR FIRE RATED - FBC TABLE 602 |
| |
| 5) BASED ON THE DISTANCE FROM THE CENTER OF THE ALLY |
| (SHOW THE DISTANCE) TO THE REAR WALL - PLEASE SHOW THE |
| ALLOWABLE NON PROTECTED OR PROTECTED OPENING |
| CALCULATIONS FOR EACH FLOOR - FBC TABLE 705.8 |
| |
| 6) PLEASE SHOW THE POOL BARRIER (DOORS, LOCKS, LATCH |
| HEIGHT ETC.) AT THE STAIR AND ELEVATOR DOORS TO COMPLY |
| WITH FBC 454.1.3.1.9 |
| |
| 7) PLEASE SHOW THE ACCESSIBLE POOL ENTRY - FBC A 242.2 |
| SWIMMING POOLS. |
| AT LEAST TWO ACCESSIBLE MEANS OF ENTRY SHALL BE |
| PROVIDED FOR SWIMMING POOLS. ACCESSIBLE MEANS OF ENTRY |
| SHALL BE SWIMMING POOL LIFTS COMPLYING WITH 1009.2; |
| SLOPED ENTRIES COMPLYING WITH 1009.3; TRANSFER WALLS |
| COMPLYING WITH 1009.4; TRANSFER SYSTEMS COMPLYING WITH |
| 1009.5; AND POOL STAIRS COMPLYING WITH 1009.6. AT LEAST |
| ONE ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL COMPLY |
| WITH 1009.2 OR 1009.3. |
| |
| 8) FOR THE REMODELED GROUND FLOOR = PLEASE SHOW THE |
| DIFFERENT DINING AREA LOCATIONS FOR THE ACCESSIBLE |
| SEATING - FBC 226 |
| |
| 9) FOR THE REMODELED GROUND FLOOR = PLEASE SHOW AT |
| LEAST 1 ACCESSIBLE SEAT AT EACH BAR LOCATION (SHOW |
| COUNTER HEIGHT, KNEE AND TOE CLEARANCES ETC. ) - FBC |
| 226.2 |
| |
| 10) PLEASE PROVIDE TYPICAL GUARDRAIL AND HANDRAIL |
| DETAILS - SHOWING HEIGHTS, OPENING SPECS., HANDRAIL |
| EXTENSIONS ETC. FBC 1014 AND 1015 |
| |
| 11) PLEASE PROVIDE A THRESHOLD INSPECTION PLAN - FBC |
| (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION PLAN. THE |
| ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO |
| PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY |
| THE ENGINEER OF RECORD. |
| |
| 12) THE STRUCTURAL DRAWINGS NEED TO CONTAIN THIS NOTE - |
| THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| |
| 13) PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER |
| THE "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS". |
| YOU CAN E MAIL ME AND ASK FOR A COPY. |
| |
| 14) PLEASE PROVIDE A COPY OF THE UNITY OF TITLE. |
| |
| 15) A SEPARATE PERMIT IS REQUIRED FOR THE BUILDING |
| DEMO. |
| |
| 16) ITEMS SUCH AS BUT NOT LIMITED TO RAILING, EXTERIOR |
| WINDOW, DOOR AND ROOFING SYSTEMS PRODUCT APPROVALS MAY |
| BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED |
| ON THE CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1 |
| DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED |
| SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL |
| REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL |
| WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| BUILDING OFFICIAL. |
| |
| 17) STRUCTURAL AND FIRE PROTECTION DRAWINGS DO NOT SHOW |
| AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED |
| DRAWINGS IN PROJECTDOX NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| SPECIFIC TYPE OF E-SIGNATURE). |
| |