2022-07-20 12:11:41 | 1ST PLUMBING REVIEW |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE |
| FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE |
| WASTE. PLEASE SHOW THAT THE ICE BINS AND HANDS SINK GO |
| TO THE SANITARY AND NOT THE GREASE WASTE. |
| |
| 2. 2017 WPB AMEND ? 107.3 - THE GREASE INTERCEPTOR |
| REQUIRES A SEPARATE PERMIT AND NEEDS TO BE APPLIED FOR |
| BEFORE THE RELEASE OF THE MASTER PERMIT. |
| |
| 3. 2020 FPC 905.4 - ON EACH END OF THE BATHROOMS, THE |
| VENT NEAR THE WATER CLOSET IS HORIZONTAL AND CANNOT BE |
| UNTIL IT IS 6? ABOVE THE FLOOD RIM OF THE FIXTURES |
| SERVED. |
| |
| 4. 2020 FPC 905.4 - THE VENTS FOR THE GREASE |
| INTERCEPTORS ARE HORIZONTAL WHILE DRY AND CANNOT BE. |
| THE VENT CANNOT BE A HORIZONTAL DRY VENT UNTIL IT IS 6? |
| ABOVE THE FLOOD RIM OF THE FIXTURES SERVED. |
| 5. WPB ORD. SEC 90 - 205 EXCEPTIONS TO DISCHARGE TO |
| STORM WATER |
| SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY |
| SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES |
| DEPARTMENT. |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| - THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| - NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| - WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL |
| OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| - DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| - FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| - FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| 6. WPB ORD. SEC. 90 - 126 - THE DISCHARGE FROM AIR |
| HANDLERS/AIR CONDITIONING CONDENSATE CANNOT DISCHARGE |
| INTO THE SANITARY. IT MUST GO TO THE STORM OR OTHER |
| APPROVED PLACE OF DISPOSAL. |
| |
| 7. 2020 FPC 419.5/607.1.2 - PLEASE INCLUDE A DETAIL |
| SHOWING COMPLIANCE WITH THE REQUIREMENTS FOR TEMPERED |
| WATER FOR PUBLIC HANDWASHING STATIONS THAT INCLUDES THE |
| LIMITING DEVICE THAT CONFORMS TO ASSE 1070. |
| |
| |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |