Plan Review Notes For Permit 22061092 |
Permit Number |
22061092 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-07-18 14:59:53 | 1ST REVIEW FMC | | PERMIT: 22061493 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE A MECHANICAL DEMO PLAN FOR THIS PROJECT. FBC | | 107.2.1 | | | | 2) PROVIDE THE ENERGY CALCULATIONS. FEC 101.5.1.1.2 | | | | 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS. FEC 403.2.1 | | | | 4) PROVIDE THE OUT DOOR AIR CALCULATIONS. FMC 403.3.1.1 | | | | 5) ADD NOTE ON THE MECHANICAL DRAWINGS INDICATING THAT | | THE HOODS AND GREASE DUCT SYSTEMS AND THE REFRIGERATION | | SYSTEMS IE WALK-IN COOLERS AND WALK-IN FREEZERS WILL | | REQUIRE A SEPARATE PERMIT AND PLAN REVIEW AND WILL NOT | | BE REVIEWED UNDER THIS PERMIT. FBC 107.2.1 | | | | 6) SHEET M-103: REVISE THE DRAWING TO SHOW THE BATHROOM | | EXHAUST FOR THE BATHROOMS IN THE DINING AREA. FMC TABLE | | 403.3.1.1 | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|