2022-06-29 13:44:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) SHEET E 000 - THERE ARE NO INDICATIONS OF FIRE ALARM |
| DEVICES, EQUIPMENT, NOR FIRE AMARM WORK |
| |
| THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT |
| DEMO & CONSTRUCTION PERIODS |
| |
| ANY WORK ON THE FIRE ALARM, INCLUDING DEMO, SHALL BE |
| DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| |
| |
| |
| 2) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF ANY |
| ELECTRICAL SHEETS SHOWING THE LOCATION OF REQUIRED EXIT |
| LIGHTS & EMERGENCY LIGHTING. |
| |
| EXIT MARKINGS, EXIT TAVEL PATH SIGNS AND EMEREGENCY |
| LIGHTING ARE REQUIRED BY NFPA 101 CH 12 NEW ASSEMBLY |
| OCCUPANCY & CH 7 MEANS OF EGRESS. |
| |
| PLEASE PROVIDE SPECIF DETAILS IN COMPLIANCE WITH THE |
| CODE. |
| |
| |
| 3) SHEET A 203 - THERE IS AN INDICATION OF POOL |
| EQUIPMENT ROOM/AREA/PLATFORM |
| |
| THE DOOR LEADING TO THIS AREA SHALL BE PLACARD PER NFPA |
| 1 & 704 FOR THE CHEMICAL STORAGE. |
| |
| |
| 3A) SHEET A 203 - PLEASE PROVIDE THE TYPE AND AMOUNT OF |
| PROPOSED CHEMICAL STORAGE IN THE POOL EQUIPMENT AREA. |
| |
| PER NFPA 1 |
| |
| |
| |
| |
| |
| WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |