Date Text
2022-07-30 18:52:32 
  
 1) 225 KVA TRANSFORMER TO BE INSTALLED PER 450.21(B)
  
 OVER 112 KVA. INDIVIDUAL DRY-TYPE TRANSFORMERS OF MORE
 THAN 112KVA RATING SHALL BE INSTALLED IN A TRANSFORMER
 ROOM
 OF FIRE-RESISTANT CONSTRUCTION. UNLESS SPECIFIED
 OTHERWISE IN THIS ARTICLE, THE TERM FIRE RESISTANT
 MEANS A CONSTRUCTION HAVING A
 MINIMUM FIRE RATING OF 1 HOUR.
  
 2) PLEASE LAYOUT ELECTRICAL ROOM IN NEW BAR AREA FOR
 WORKING CLEARANCES AND OVERHEAD CLEARANCES FOR
 MECHANICAL EQUIPMENT. 110.26
  
 3) ALL OUTDOOR OUTLETS 125, AND 240 VOLT TO BE GFCI
 PROTECTED PER 210.8(B) 50 AMPERES SINGLE PHASE AND 100
 AMPERES FOR THREE PHASE.
  
 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50
 AMPERES OR LESS AND THREEPHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100
 AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS
 SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
  
 RECEPTACLES OF 15 AND 20 AMPERES IN A WET LOCATION.
 RECEPTACLES OF 15 AND 20 AMPERES, 125 AND 250 VOLTS
 INSTALLED
 IN A WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS
 WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS
 INSERTED. AN OUTLET
 BOX HOOD INSTALLED FOR THIS PURPOSE SHALL BE LISTED AND
 SHALL BE IDENTIFIED AS ?EXTRA-DUTY.? OTHER LISTED
 PRODUCTS, ENCLOSURES, OR
 ASSEMBLIES PROVIDING WEATHERPROOF PROTECTION THAT DO
 NOT UTILIZE AN OUTLET BOX HOOD NEED NOT BE MARKED
 ?EXTRA DUTY.?
  
 4) RECEPACLES THAT LOOK LIKE THEY ARE FLOOR BOXES IN
 THE POOL AREA DECK AND OTHER AREAS ON ROOF DECK PLEASE
 SHOW DETAIL. 406.9
  
 5) COVERS FOR RECEPATCLES INSTALLED IN DAMP/WET
 LOCATION SHALL MEET THE REQUIREMENTS OF 406.9(A)
  
 406.9(A) DAMP LOCATIONS. A RECEPTACLE INSTALLED
 OUTDOORS IN A LOCATION PROTECTED FROM THE WEATHER OR IN
 OTHER DAMP LOCATIONS
 SHALL HAVE AN ENCLOSURE FOR THE RECEPTACLE THAT IS
 WEATHERPROOF WHEN THE RECEPTACLE IS COVERED (ATTACHMENT
 PLUG CAP NOT
 INSERTED AND RECEPTACLE COVERS CLOSED).
  
 6) SOME OF THE SPEAKERS ARE ON 120 VOLT CIRCUITS AND
 SOME ARE NOT, PLEASE DISGUIGUISH BETWEEN THE TYPES
 110.3
  
 7) FANS INSTALLED AROUND POOL NEED TO SHOW DISTANCE AND
 HEIGHT FROM POOL. 680.22(B)(1)
  
 8) MDP1LOAD CALCULATION SHOWS EXISTING? I DO NOT SEE
 PANELS A,B AND OTHER LOADS NOT LISTED ON PANEL SCHEDULE
 FOR MDP1. 220
 PLEASE SHOW HOW THE LOAD CALCULATION WAS ARRIVED AT FOR
 MDP1, AND MDP2 YOU CAN NOT USE A DEMAND ON A PANEL THAT
 WAS
 ALREADY DEMANDED WHEN SIZING THE PANEL.
  
 9) IS THE VIP LEVEL AND THE ROOF LEVEL THE SAME?
  
 10) NEED A LAYOUT OF THE POOL EQUIPMENT ON PLAN.
  
  