2022-07-30 18:52:32 | |
| |
| 1) 225 KVA TRANSFORMER TO BE INSTALLED PER 450.21(B) |
| |
| OVER 112 KVA. INDIVIDUAL DRY-TYPE TRANSFORMERS OF MORE |
| THAN 112KVA RATING SHALL BE INSTALLED IN A TRANSFORMER |
| ROOM |
| OF FIRE-RESISTANT CONSTRUCTION. UNLESS SPECIFIED |
| OTHERWISE IN THIS ARTICLE, THE TERM FIRE RESISTANT |
| MEANS A CONSTRUCTION HAVING A |
| MINIMUM FIRE RATING OF 1 HOUR. |
| |
| 2) PLEASE LAYOUT ELECTRICAL ROOM IN NEW BAR AREA FOR |
| WORKING CLEARANCES AND OVERHEAD CLEARANCES FOR |
| MECHANICAL EQUIPMENT. 110.26 |
| |
| 3) ALL OUTDOOR OUTLETS 125, AND 240 VOLT TO BE GFCI |
| PROTECTED PER 210.8(B) 50 AMPERES SINGLE PHASE AND 100 |
| AMPERES FOR THREE PHASE. |
| |
| 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE |
| RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50 |
| AMPERES OR LESS AND THREEPHASE |
| RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100 |
| AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS |
| SHALL HAVE GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| |
| RECEPTACLES OF 15 AND 20 AMPERES IN A WET LOCATION. |
| RECEPTACLES OF 15 AND 20 AMPERES, 125 AND 250 VOLTS |
| INSTALLED |
| IN A WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS |
| WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS |
| INSERTED. AN OUTLET |
| BOX HOOD INSTALLED FOR THIS PURPOSE SHALL BE LISTED AND |
| SHALL BE IDENTIFIED AS ?EXTRA-DUTY.? OTHER LISTED |
| PRODUCTS, ENCLOSURES, OR |
| ASSEMBLIES PROVIDING WEATHERPROOF PROTECTION THAT DO |
| NOT UTILIZE AN OUTLET BOX HOOD NEED NOT BE MARKED |
| ?EXTRA DUTY.? |
| |
| 4) RECEPACLES THAT LOOK LIKE THEY ARE FLOOR BOXES IN |
| THE POOL AREA DECK AND OTHER AREAS ON ROOF DECK PLEASE |
| SHOW DETAIL. 406.9 |
| |
| 5) COVERS FOR RECEPATCLES INSTALLED IN DAMP/WET |
| LOCATION SHALL MEET THE REQUIREMENTS OF 406.9(A) |
| |
| 406.9(A) DAMP LOCATIONS. A RECEPTACLE INSTALLED |
| OUTDOORS IN A LOCATION PROTECTED FROM THE WEATHER OR IN |
| OTHER DAMP LOCATIONS |
| SHALL HAVE AN ENCLOSURE FOR THE RECEPTACLE THAT IS |
| WEATHERPROOF WHEN THE RECEPTACLE IS COVERED (ATTACHMENT |
| PLUG CAP NOT |
| INSERTED AND RECEPTACLE COVERS CLOSED). |
| |
| 6) SOME OF THE SPEAKERS ARE ON 120 VOLT CIRCUITS AND |
| SOME ARE NOT, PLEASE DISGUIGUISH BETWEEN THE TYPES |
| 110.3 |
| |
| 7) FANS INSTALLED AROUND POOL NEED TO SHOW DISTANCE AND |
| HEIGHT FROM POOL. 680.22(B)(1) |
| |
| 8) MDP1LOAD CALCULATION SHOWS EXISTING? I DO NOT SEE |
| PANELS A,B AND OTHER LOADS NOT LISTED ON PANEL SCHEDULE |
| FOR MDP1. 220 |
| PLEASE SHOW HOW THE LOAD CALCULATION WAS ARRIVED AT FOR |
| MDP1, AND MDP2 YOU CAN NOT USE A DEMAND ON A PANEL THAT |
| WAS |
| ALREADY DEMANDED WHEN SIZING THE PANEL. |
| |
| 9) IS THE VIP LEVEL AND THE ROOF LEVEL THE SAME? |
| |
| 10) NEED A LAYOUT OF THE POOL EQUIPMENT ON PLAN. |
| |
| |