Plan Review Notes For Permit 22061083 |
Permit Number |
22061083 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-07-20 16:42:52 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FS471, THE DOCUMENT IS REQUIRED TO BE DIGITALLY | | SIGNED. IT APPEARS THAT THE DOCUMENT WAS DIGITALLY | | SIGNED, PRINTED, SUBMITTED PAPER, THEN SCANNED. UPLOAD | | THE DIGITALLY SIGNED PDFS PROVIDED BY THE ENGINEER. IF | | YOU WOULD LIKE FOR ME TO VERIFY THE DIGITAL SIGNATURE | | PRIOR TO RESUBMITTING, EMAIL TO [email protected]. | | | | 2. GENERAL NOTE 1, FBC R 4501.6, REVISE NOTE TO INCLUDE | | ANSI/NSPI-6. | | | | 3. FBC R 301, REVISE EQUIPMENT ANCHORING DETAIL TO | | SPECIFY TAPCON LENGTH AND DIAMETER. | | | | | | | | | | | | | | | | |
|