Plan Review Notes
Plan Review Notes For Permit 22061077
Permit Number 22061077
Review Stop P
Sequence Number 2
Notes
Date Text
2023-02-09 14:26:172ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22061077
 2/9/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-1 WHICH HAS THE PLUMBING RISER AND WATER
 HEATER SCHEDULE WAS SUBMITTED ELECTRONICALLY HOWEVER
 THE PLAN SHEET IS NOT DIGITALLY SIGNED AND SEALED BY
 THE ENGINEER OF RECORD AS REQUIRED BY FL. STATUTE
 471.025 AND SECTION 61G15-23.005 FAC. AS PREVIOUSLY
 NOTED THE WASHING MACHINE STANDPIPE SHALL BE 2-INCH
 HOWEVER THE PLAN IS STILL SHOWING 1-1/2 INCH- TABLE
 P3201.7 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  