Plan Review Notes For Permit 22061077 |
Permit Number |
22061077 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-02-09 14:26:17 | 2ND REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 22061077 | | 2/9/23 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET E-1 WHICH HAS THE PLUMBING RISER AND WATER | | HEATER SCHEDULE WAS SUBMITTED ELECTRONICALLY HOWEVER | | THE PLAN SHEET IS NOT DIGITALLY SIGNED AND SEALED BY | | THE ENGINEER OF RECORD AS REQUIRED BY FL. STATUTE | | 471.025 AND SECTION 61G15-23.005 FAC. AS PREVIOUSLY | | NOTED THE WASHING MACHINE STANDPIPE SHALL BE 2-INCH | | HOWEVER THE PLAN IS STILL SHOWING 1-1/2 INCH- TABLE | | P3201.7 FBC P. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|