2022-08-03 17:06:20 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22061077 809 VALLEY FORGE RD |
| |
| 1- PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE |
| DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT |
| WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES. |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC. |
| 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| |
| 2- -PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| R101.5 FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL |
| THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED |
| AGENT TO AVOID CONFLICT/DELAYS. |
| |
| 3- OFFICE DOESN'T COMPLY WITH THE MINIMUM ROOM |
| DIMENSION REQUIRED BY SEC. R304.2 FBC-RESIDENTIAL. |
| REVISE AS REQUIRED. |
| |
| 4- SPECIFY HOW PROVIDING HEAT TO ALL HABITABLE AREAS AS |
| REQUIRED BY SEC. R303.10 FBC-RESIDENTIAL. |
| |
| 5- ENGINEER OF RECORD TO SPECIFY ALL ROOF LIVE AND DEAD |
| LOADS. CLEARLY SPECIFY TRUSS TOP CHORD LIVE AND DEAD |
| LOADS AND BOTTOM CHORD LIVE AND DEAD LOADS. NOTE: |
| INCLUDE THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 |
| FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G". |
| |
| 6- SOUTH ELEVATION ON SHEET A-1: WINDOWS ARE LOCATED IN |
| THE END ZONE NOT INTERIOR ZONE. REVISE AS REQUIRED. |
| FIGURE R301.2(7) FBC-RESIDENTIAL. |
| NOTE: SAME COMMENT APPLIES TO KITCHEN WINDOW ON EAST |
| ELEVATION. |
| |
| 7- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807.1 |
| FBC-RESIDENTIAL. |
| |
| 8- SHEET S-2: |
| A) CLARIFY CONSTRUCTION AT THE GABLE END. ROOF FRAMING |
| PLAN SPECIFIES STRUCTURAL GABLE END TRUSS BUT IT ALSO |
| CALLS FOR DETAIL 2/S-3. THERE IS NO DETAIL 2/S-3 BUT |
| THERE IS DETAIL 1-S-3 FOR RAKE BEAM. REVISE/CLARIFY AS |
| REQUIRED AND CORRECT DETAIL NUMBER IF USING RAKE BEAM |
| DETAIL. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B) WIND RESISTANCE OF EXTERIOR SOFFITS: ENGINEER OF |
| RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| FOR THE SOFFIT CONSTRUCTION AT PORCH AND ROOF EAVES |
| SHOWING COMPLIANCE WITH SEC. R704 FBC-RESIDENTIAL. |
| NOTE: IF USING STUCCO, THEN, PROVIDE SPECIFICATIONS |
| SHOWING COMPLIANCE WITH ASTM C1063 (SEE TABLE 3 OF ASTM |
| C1063). |
| |
| C) ATTIC VENTILATION CALCULATIONS CALL FOR SOFFIT VENTS |
| AND RIDGE VENTS. CLEARLY SPECIFY SIZE AND LOCATION OF |
| VENTS. NOTE: TYPICAL WALL SECTION ON SHEET S-3 CALL FOR |
| CONTINUOUS SOFFIT VENT. SPECIFY SIZE OF SOFFIT VENT AND |
| SPECIFY SIZE AND LOCATION OF RIDGE VENTS ON THE ROOF |
| FRAMING PLAN. |
| SEC. R806 FBC-RESIDENTIAL. |
| |
| 9-ROOFING UNDERLAYMENT |
| PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE |
| NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. |
| SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| FBC-RESIDENTIAL IS GOING TO BE USED. |
| |
| 10- BUILDING DIMENSIONS SHOWN ON THE FLOOR PLAN ON |
| SHEET A-3 AND BUILDING DIMENSIONS SHOWN ON THE SURVEY |
| SUBMITTED DON'T MATCH. REVISE AS REQUIRED TO MATCH. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 11- PRODUCT APPROVALS |
| PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)METAL ROOF. |
| |
| B)RIDGE VENTS FOR METAL ROOF AS SPECIFIED ON PLANS. |
| |
| C)ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS. |
| |
| D)SINGLE HUNG WINDOWS. |
| |
| E)FIXED WINDOWS. |
| |
| F)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE CITY SAMPLE. |
| |
| G)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. |
| |
| 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 13- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. VALUATION WAS UPDATED TO $118,287.00. THE |
| PERMIT FEE BALANCE IS $753.83 |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |