Plan Review Notes
Plan Review Notes For Permit 22061077
Permit Number 22061077
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-03 17:06:20RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061077 809 VALLEY FORGE RD
  
 1- PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC.
 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 2- -PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL
 THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED
 AGENT TO AVOID CONFLICT/DELAYS.
  
 3- OFFICE DOESN'T COMPLY WITH THE MINIMUM ROOM
 DIMENSION REQUIRED BY SEC. R304.2 FBC-RESIDENTIAL.
 REVISE AS REQUIRED.
  
 4- SPECIFY HOW PROVIDING HEAT TO ALL HABITABLE AREAS AS
 REQUIRED BY SEC. R303.10 FBC-RESIDENTIAL.
  
 5- ENGINEER OF RECORD TO SPECIFY ALL ROOF LIVE AND DEAD
 LOADS. CLEARLY SPECIFY TRUSS TOP CHORD LIVE AND DEAD
 LOADS AND BOTTOM CHORD LIVE AND DEAD LOADS. NOTE:
 INCLUDE THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5
 FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G".
  
 6- SOUTH ELEVATION ON SHEET A-1: WINDOWS ARE LOCATED IN
 THE END ZONE NOT INTERIOR ZONE. REVISE AS REQUIRED.
 FIGURE R301.2(7) FBC-RESIDENTIAL.
 NOTE: SAME COMMENT APPLIES TO KITCHEN WINDOW ON EAST
 ELEVATION.
  
 7- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807.1
 FBC-RESIDENTIAL.
  
 8- SHEET S-2:
 A) CLARIFY CONSTRUCTION AT THE GABLE END. ROOF FRAMING
 PLAN SPECIFIES STRUCTURAL GABLE END TRUSS BUT IT ALSO
 CALLS FOR DETAIL 2/S-3. THERE IS NO DETAIL 2/S-3 BUT
 THERE IS DETAIL 1-S-3 FOR RAKE BEAM. REVISE/CLARIFY AS
 REQUIRED AND CORRECT DETAIL NUMBER IF USING RAKE BEAM
 DETAIL. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) WIND RESISTANCE OF EXTERIOR SOFFITS: ENGINEER OF
 RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE SOFFIT CONSTRUCTION AT PORCH AND ROOF EAVES
 SHOWING COMPLIANCE WITH SEC. R704 FBC-RESIDENTIAL.
 NOTE: IF USING STUCCO, THEN, PROVIDE SPECIFICATIONS
 SHOWING COMPLIANCE WITH ASTM C1063 (SEE TABLE 3 OF ASTM
 C1063).
  
 C) ATTIC VENTILATION CALCULATIONS CALL FOR SOFFIT VENTS
 AND RIDGE VENTS. CLEARLY SPECIFY SIZE AND LOCATION OF
 VENTS. NOTE: TYPICAL WALL SECTION ON SHEET S-3 CALL FOR
 CONTINUOUS SOFFIT VENT. SPECIFY SIZE OF SOFFIT VENT AND
 SPECIFY SIZE AND LOCATION OF RIDGE VENTS ON THE ROOF
 FRAMING PLAN.
 SEC. R806 FBC-RESIDENTIAL.
  
 9-ROOFING UNDERLAYMENT
 PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE
 NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT.
 SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED.
  
 10- BUILDING DIMENSIONS SHOWN ON THE FLOOR PLAN ON
 SHEET A-3 AND BUILDING DIMENSIONS SHOWN ON THE SURVEY
 SUBMITTED DON'T MATCH. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 11- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)METAL ROOF.
  
 B)RIDGE VENTS FOR METAL ROOF AS SPECIFIED ON PLANS.
  
 C)ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS.
  
 D)SINGLE HUNG WINDOWS.
  
 E)FIXED WINDOWS.
  
 F)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 G)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 13- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $118,287.00. THE
 PERMIT FEE BALANCE IS $753.83
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  