2023-01-31 10:42:06 | 4TH REVIEW FMC |
| PERMIT: 22061010 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS |
| NOW INDICATED BARBER SHOP. THE PREVIOUS SUBMITTAL DID |
| SHOW MANICURE STATIONS. FMC TABLE 403.3.1.1 |
| |
| 2) THE REVIEWER NOTES SUBMITTED THIS CYCLE HAS A |
| MECHANICAL REVIEW DATE OF 08/08/2022, THIS IS NOT THE |
| MOST RECENT REVIEW COMMENTS. THE MOST RECENT MECHANICAL |
| REVIEW COMMENTS ARE DATED 1/12/2023 AND THERE ARE 6 |
| COMMENTS THAT WOULD NEED TO BE ADDRESSED. PLEASE SEE |
| BELOW: |
| 3RD REVIEW FMC |
| PERMIT: 22061010 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) I CANNOT DO A COMPLETE REVIEW UNTIL A COMPLETE |
| DESIGN FOR THIS TENANT IS DESIGNED AND SUBMITTED. |
| |
| 2) THE PERMIT APPLICATION SHOULD REFLECT WHAT IS BEING |
| BROUGHT INTO THIS TENANT SPACE. CORRECT THE |
| APPLICATION. |
| |
| 3) PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS NEW |
| TENANT. THE UPSTAIRS WAS FOR THE LIVE AND THE MAIN |
| FLOOR WAS FOR THE BUSINESS. IT APPEARS THAT NOW THE |
| ENTIRE TENANT SPACE IS TO BE A BEAUTY SALON WITH |
| MANICURE STATIONS. THIS REQUIRES MORE EXHAUST THAN THE |
| ORIGINAL DESIGN OF THIS SPACE HAS NOW. FBC 107.3.5 |
| |
| PROVIDE THE MECHANICAL EQUIPMENT SIZING FOR THIS CHANGE |
| OF USE. PROVIDE A COMPLETE EXHAUST DESIGN FOR THE |
| MANICURE STATIONS. IS THERE TO BE PEDICURE STATIONS AS |
| WELL? IF SO SHOW THE DESIGN FOR THIS AS WELL. |
| 502.20 MANICURE AND PEDICURE STATIONS. MANICURE AND |
| PEDICURE STATIONS SHALL BE PROVIDED WITH AN EXHAUST |
| SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1, NOTE H. |
| MANICURE TABLES AND PEDICURE STATIONS NOT PROVIDED WITH |
| FACTORY-INSTALLED EXHAUST INLETS SHALL BE PROVIDED WITH |
| EXHAUST INLETS LOCATED NOT MORE THAN 12 INCHES (305 MM) |
| HORIZONTALLY AND VERTICALLY FROM THE POINT OF CHEMICAL |
| APPLICATION. |
| |
| 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE ENTIRE |
| TENANT SPACE FOR EACH USE OF SPACE. USE THE OCCUPANCY |
| CLASSIFICATION FROM TABLE 403.3.1.1 FOR THE OCCUPANCY |
| USE OF EACH SPACE. |
| |
| 5) THE UPSTAIRS BATHROOM APPEARS TO NOW BE FOR THE |
| PUBLIC. SHOW THAT THE BATHROOM EXHAUST FAN WILL MEET |
| THE EXHAUST REQUIREMENTS FROM TABLE 403.3.1.1 |
| |
| 6) THE NEW O/A GRILL APPEARS TO BE COMING FROM THE A/C |
| CLOSET. HOW IS THIS OUTDOOR AIR BEING CONDITIONED? |
| TYPICALLY, THE OUTDOOR AIR IS BROUGHT INTO THE RETURN |
| AIR DUCT AT THE MECHANICAL SYSTEM FROM THE EXTERIOR OF |
| THE BUILDING. SHOW THE DUCT SIZE ON THE DRAWING FOR THE |
| OUTDOOR AIR. FBC 107.3.5 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |