2022-12-08 09:46:572ND REVIEW FBC-2020 PLUMBING
 PERMIT-22061010
 12/8/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1: THE RESUBMITTED PLAN IS SHOWING MOEN
 SHOWER VALVES TO BE INSTALLED AS MIXING VALVES FOR THE
 SHAMPOO SINKS WHICH ARE NOT IN COMPLIANCE WITH SEC.
 607.1.1 FBC P AND 412.10 HEAD SHAMPOO SINK FAUCETS.
 HEAD SHAMPOO SINK FAUCETS SHALL BE SUPPLIED WITH HOT
 WATER THAT IS LIMITED TO A MAXIMUM TEMPERATURE OF
 120??F BY A WATER-TEMPERATURE-LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. EACH FAUCET SHALL
 HAVE INTEGRAL CHECK VALVES TO PREVENT CROSSOVER FLOW
 BETWEEN THE HOT AND COLD WATER SUPPLY CONNECTIONS.
  
 2) BASED ON THE BUILDING REVIEWER'S COMMENTS REQUIRING
 ACCESSIBLE BATHROOM FIXTURES IT APPEARS CHANGES WILL BE
 MADE TO DRAWINGS WHICH WILL REQUIRE FURTHER PLUMBING
 REVIEW- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  