Plan Review Notes For Permit 22061010 |
Permit Number |
22061010 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-12-14 11:00:52 | PLEASE ADDRESS FIRST CYCLE COMMENTS LISTED BELOW: | | | | | | 2) WHAT IS THE PREVIOUS USE OF SPACE IN THE WORK AREA? | | | | 3) IS THE NEW WORK AREA TO BE A BEAUTY SALON? IF SO | | PROVIDE THE OUTDOOR AIR AND EXHAUST CALCULATIONS FOR | | THIS BEAUTY SALON. FMC 403.3.1.1 | | | | PLEASE ADD EXPLAINATORY NOTES TO THE SUBMITTED M-1 | | SHEET. IT IS UNCLEAR TO THIS REVIEWER AS TO HOW THE O/A | | IS BEING INTRODUCED TO THIS UNIT. IT APPEARS THAT IT IS | | NOT BEING INTRODUCED INTO THE MECHANICAL SYSTEM. PLEASE | | SHOW THAT THIS O/A DUCT IS TO BE CONNECTED TO THE | | MECHANICAL SYSTEM RETURN. FMC 403.3.1.1 | | | | PROVIDE A DETAIL FOR THE NEW 360 CFM EXHAUST FAN TYING | | INTO THE EXHISTING EXHAUST VENT SHAFT. EXPLAIN WHY 360 | | CFM'S OF EXHAUST IS REQUIRED. FBC 107.3.5 |
|