2022-06-28 14:00:161ST REVIEW FBC-2020 PLUMBING
 PERMIT-22061160
 6/28/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1: PROVIDE A MEANS OF LIMITING THE HOT WATER
 DELIVERY TEMPERATURE AT THE SINKS- SEC. 607.1.1 FBC P.
 PLEASE NOTE THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING MEANS.
  
 2) P-1: PROVIDE A FIXTURE SCHEDULE ON THE PLAN THAT
 INCLUDES THE SINKS AND THE FAUCETS- SECS. 422.1 & 412.1
 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  