2022-08-29 08:20:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. FBC R 310.4, REVISE PLAN TO SHOW EMERGENCY ESCAPE
 OPENING. THE PLAN SHOWS THAT THE FRONT DOOR WILL BE
 COVERED. IT IS NOT CLEAR IF THE DOOR WILL REMAIN
 OPERABLE. IF YES, NOTE ON PLAN. IF NO, INDICATE THE
 OPENING ON THE PLAN.
  
 3RD REVIEW:
  
 NOTHING WAS NOTED ON THE SITE PLAN. THE PLAN SHOWS TWO
 OPENINGS TO BE COVERED - NO 1, A RECESSED DOOR. NO 2,
 ANOTHER OPENING THAT IS MARKED "FRONT ENTRY". SEE THE
 PRODUCT APPROVAL FL812.1, SHEET 3 OF 9. SOMEONE CIRCLED
 A DETAIL WHICH APPEARS TO PROPOSE INSTALLATION FROM THE
 TRUSS TO THE FOOTER. THEREFORE IT APPEARS THAT EXITING
 FROM THE RECESSED DOOR IS OBSTRUCTED.
  
 REVISE PLAN TO SHOW THE EMERGENCY ESCAPE OPENING. THIS
 CAN BE ANOTHER OPENING IN THE HOUSE. INCLUDE THE ROOM
 DESIGNATION.
  
 2. NEW COMMENT - INSTALLATION SCHEDULE PROPOSES
 HORIZONTAL INSTALLATION INTO CONCRETE. THIS IS IN
 CONFLICT WITH THE DETAIL CIRCLED ON SHEET 3. FBC 107,
 CLARIFY.
  