Plan Review Notes For Permit 22060913 |
Permit Number |
22060913 |
|
Review Stop |
R |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2023-05-11 18:06:17 | ROOFING REVIEW: | | | | 1- PRODUCT APPROVALS | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR: | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | 2-- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | | | | | | | |
|