2023-05-11 17:53:28 | NEW SINGLE FAMILY RESIDENCE(R3) FOURTH BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22060913 |
| 922 AVON RD |
| |
| ORIGINAL COMMENT: |
| 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| R101.5 FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| PREVIOUS COMMENT: |
| RESPONSE: [ COMMENTS NOT ADDRESSED.] |
| ENERGY CALCULATIONS SUBMITTED: |
| A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM |
| THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS |
| PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| NEW RESPONSE ON 05/11/23: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| NEW RESPONSE ON 05/11/23: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| C)CEILING INFORMATION ON ITEM #11 DOESN'T MATCH PLANS. |
| PLANS SHOW VENTED ATTIC AND ROOF INSULATION. |
| |
| NEW RESPONSE ON 05/11/23: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| D) WINDOWS ORIENTATION AND AREA DON'T MATCH PLANS. |
| REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| NEW RESPONSE ON 05/11/23: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY |
| CONSERVATION. |
| |
| NEW RESPONSE ON 05/11/23: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| NEW COMMENT BASED ON REVISED PLANS: |
| F)REVISE SPACES INFORMATION ON PAGE 2. NEW PLANS DON'T |
| SHOW A KITCHEN ANYMORE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| 7- GUEST HOUSE ROOF FRAME DETAIL PLAN. |
| ORIGINAL COMMENT: |
| D)SPECIFY ROOF SHEATHING NAILING SPECIFICATIONS TO |
| COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. |
| SPECIFY THICKNESS, NAIL TYPE, SIZE AND SPACING. NOTE: |
| NEED TO USE RING SHANK NAILS. ROOF SHEATHING NEEDS TO |
| BE NAILED AT 4 INCHES O.C. IN THE FIELD AND EDGES AS |
| REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1 |
| FBC-RESIDENTIAL. |
| |
| PREVIOUS COMMENT: |
| RESPONSE: [ NOT RESOLVED.] |
| ROOF SHEATHING SPECIFICATIONS SHOWN ON THE COMPONENT |
| AND CLADDING PRESSURE ZONES ON SHEET S.3. DON'T COMPLY |
| WITH TABLE R803.2.3.1 FBC-RESIDENTIAL. REVISE AS |
| REQUIRED. |
| NOTE: COORDINATE WITH ITEM 4(B) ABOVE. |
| |
| NEW RESPONSE ON 05/11/23: |
| NEW DESIGNER OF RECORD. REVISE THE ROOF NAILING PATTERN |
| SPECIFIED ON SHEET S-3 UNDER "MAX. COMPONENTS AND |
| CLADDING DESIGN WIND PRESSURES". SPECIFICATIONS ARE |
| INCOMPLETE. IT ONLY SPECIFIES THE SPACING AT THE EDGE. |
| NEED TO PROVIDE ROOF SHEATHING NAILING SPECIFICATIONS |
| FOR ALL ROOF ZONES. TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| NOTE: PLYWOOD ROOF SHEATHING NAILING IS REQUIRED ALL |
| THE TIME. IT IS NOT CLEAR WHY ARCHITECT WROTE NOTE "IF |
| REQUIRED". CLARIFY AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| ORIGINAL COMMENTS: |
| 16- PRODUCT APPROVALS |
| PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| ORIGINAL COMMENT: |
| A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. |
| |
| PREVIOUS COMMENT: |
| RESPONSE: [ NOT RESOLVED. THE C & C PRESSURES SPECIFIED |
| ON SHEET S.1 FOR THE DOORS AND WINDOWS ARE QUITE HIGH |
| FOR A BUILDING LESS THAN 15 FT IN HEIGHT. ] |
| REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR IS NOT |
| SPECIFYING IF SUBMITTING NOW OR LATER AS DEFERRED |
| SUBMITTAL. |
| |
| NEW RESPONSE ON 05/11/23: |
| REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR IS NOT |
| SPECIFYING IF SUBMITTING NOW OR LATER AS DEFERRED |
| SUBMITTAL. |
| NOTE: PRODUCT APPROVAL NEEDS TO BE REVIEWED AND |
| APPROVED IN WRITING (NOT SIGNING AND SEALING) BY |
| DESIGNER OF RECORD AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| PREVIOUS COMMENT: |
| B)SLIDING GLASS DOORS THAT MEET THE DESIGN PRESSURES |
| CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1 |
| DRAWING. |
| |
| NEW RESPONSE ON 05/11/23: |
| PRODUCT APPROVAL NEEDS TO BE REVIEWED AND APPROVED IN |
| WRITING (NOT SIGNING AND SEALING) BY DESIGNER OF RECORD |
| AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| PREVIOUS COMMENT: |
| C)SINGLE HUNG WINDOWS THAT MEET THE DESIGN PRESSURES |
| CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1 |
| DRAWING. |
| |
| NEW RESPONSE ON 05/11/23: |
| PRODUCT APPROVAL NEEDS TO BE REVIEWED AND APPROVED IN |
| WRITING (NOT SIGNING AND SEALING) BY DESIGNER OF RECORD |
| AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| PREVIOUS COMMENT: |
| D)ENTRY DOOR THAT MEET THE DESIGN PRESSURES CALCULATED |
| BY THE ENGINEER OF RECORD ON REVISED S.1 DRAWING. |
| |
| NEW RESPONSE ON 05/11/23: |
| REPEAT COMMENT. NO SUBMITTED AND PRODUCT APPROVAL NEEDS |
| TO BE REVIEWED AND APPROVED IN WRITING (NOT SIGNING AND |
| SEALING) BY DESIGNER OF RECORD AS REQUIRED BY SEC. |
| 107.3.4.1 CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 17- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| |
| NEW COMMENTS BASED ON REVISED DRAWINGS BY NEW DESIGNER |
| OF RECORD: |
| 18- FLOOR PLAN LAYOUT WAS CHANGED BUT NEW ELECTRICAL, |
| PLUMBING AND MECHANICAL PLANS WERE NOT SUBMITTED. NEED |
| TO PROVIDE REVISED PLANS FOR ALL TRADES. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| 19- REVISE THE ROOF DESIGN PRESSURES SPECIFIED ON SHEET |
| S-3 UNDER "MAX. COMPONENTS AND CLADDING DESIGN WIND |
| PRESSURES". SPECIFICATIONS ARE TOO LOW FOR BUILDING |
| EXPOSURE "C". |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 20- REVISE VENTING SPECIFICATIONS ON THE TYPICAL WALL |
| SECTION ON SHEET S-2. |
| 7"X24" VENTS AT 4'-0" O.C. DON'T ALLOW CROSS |
| VENTILATION. THE ROOF IS FRAMED WITH 2X10'S AT 16" |
| O.C.. REVISE AS REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |
| |