Plan Review Notes
Plan Review Notes For Permit 22060913
Permit Number 22060913
Review Stop B
Sequence Number 2
Notes
Date Text
2022-10-21 17:38:49NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22060913
 922 AVON RD
  
 ORIGINAL COMMENT:
 1- LOT DRAINAGE
 PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC.
 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED:
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM
 THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS
 PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C)CEILING INFORMATION ON ITEM #11 DOESN'T MATCH PLANS.
 PLANS SHOW VENTED ATTIC AND ROOF INSULATION.
 NOTE: COORDINATE WITH ENGINEER OF RECORD BECAUSE PLANS
 WILL NEED TO BE REVISED. THEY ARE NO CORRECT ON TYPE OF
 VENTILATION AND CEILING INSULATION. SEE COMMENTS BELOW.
  
 D) WINDOWS ORIENTATION AND AREA DON'T MATCH PLANS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 3- OK.
  
 4- WIND LOAD SCHEDULE.
 A)OK.
  
 ORIGINAL COMMENT:
 B)ROOF DIAGRAM SHOWN UNDER THE WIND LOAD SCHEDULE
 DOESN'T CORRESPOND TO ROOF TYPE SHOWN ON PLANS
 SUBMITTED. SEE FIGURE R301.2(7) FBC-RESIDENTIAL OF
 CURRENT CODE AND REVISE AS REQUIRED TO MATCH PROPOSED
 ROOF TYPE.
  
 RESPONSE:
 ROOFS DIAGRAMS SHOWN ON NEW SHEET S.3 DON'T MATCH
 CURRENT CODE REVISED FIGURE R301.2(7) FBC-RESIDENTIAL.
 REVISE AS REQUIRED. SHOW ALL NEW ZONES.
  
 5- GUEST HOUSE DIMENSIONS FLOOR PLAN:
 ORIGINAL COMMENT:
 A)ENTRY DOOR DOESN'T COMPLY WITH THE MIN. CLEAR WIDTH
 OF 32" AS REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL.
 REVISE AS REQUIRED.
  
 RESPONSE:
 COORDINATE WITH ITEM 5(B) BELOW.
  
 ORIGINAL COMMENT:
 B) PROVIDE DOOR AND WINDOW SCHEDULE (NOTE: INCLUDE
 INTERIOR DOORS). SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 DOORS/WINDOWS SHOWN ON THE DOOR/WINDOW SCHEDULES ARE
 NOT KEYED ON THE FLOOR PLAN. CLEARLY KEY THEM ON BOTH
 TO AVOID CONFLICTS/CONFUSION. IT LOOKS LIKE THE ENTRY
 DOOR IS SPECIFIED AS 32" X84" ALU DOOR. THIS DOOR
 DOESN'T COMPLY WITH THE REQUIRED EGRESS DOOR. ALSO,
 NEED TO REVISE THE DOOR OPENING DIMENSION SHOWN ON THE
 GUEST HOUSE DIMENSION FLOOR PLAN.
 NOTE: COORDINATE INFORMATION ON GUEST HOUSE DIMENSION
 FLOOR PLAN, DOOR AND WINDOW SCHEDULES (CHECK SIZES) AND
 NEW PLAN VIEW ON SHEET S.1 TO AVOID MORE
 CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 C) NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A
 DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED
 BY SEC. R320.1.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 30" DOOR DOESN???T COMPLY. REVISE AS REQUIRED. NEED
 DOOR THAT PROVIDES 29" MIN. CLEAR OPENING. REVISE AS
 REQUIRED. TYPICALLY 32" DOORS ARE THE ONES COMPLYING.
  
 ORIGINAL COMMENT:
 6- PLOT PLAN 1/S1 ON SHEET 1/5: SPECIFY NEW HOUSE
 CONSTRUCTION SETBACKS TO PROPERTY LINES AND EXISTING
 MAIN HOUSE. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 HOUSE GUEST HOUSE ADDITION LAYOUT SUBMITTED IS TOO
 SCHEMATIC. PROVIDE COMPLETE SITE PLAN BASED ON SURVEY
 SHOWING ACTUAL DIMENSIONS. SEC. 107.3.5.3 CITY
 AMENDMENTS.
  
 7- GUEST HOUSE ROOF FRAME DETAIL PLAN.
  
 ORIGINAL COMMENT:
 D)SPECIFY ROOF SHEATHING NAILING SPECIFICATIONS TO
 COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS.
 SPECIFY THICKNESS, NAIL TYPE, SIZE AND SPACING. NOTE:
 NEED TO USE RING SHANK NAILS. ROOF SHEATHING NEEDS TO
 BE NAILED AT 4 INCHES O.C. IN THE FIELD AND EDGES AS
 REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 SPECIFICATIONS SHOWN ON THE COMPONENT AND CLADDING
 PRESSURE ZONES ON SHEET S.3. DON'T COMPLY WITH TABLE
 R803.2.3.1 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 NTE: COORDINATE WITH ITEM 4(B) ABOVE.
  
 8-12 OK.
  
 ORIGINAL COMMENT:
 13-R-30 BATT INSULATION DOESN'T FIT ON 2X4 ROOF JOIST.
 REVISE AS REQUIRED. COORDINATE WITH SPECIFIED CROSS
 VENTILATION.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 REVISED DRAWINGS DON'T PROVIDE ANY INFORMATION FOR
 CEILING INSULATION.
 REVISE TYPICAL WALL SECTION TO INCLUDE:
 A)CEILING INSULATION TYPE AND R-VALUE.
 B)WALL INSULATION TYPE AND R-VALUE.
  
 ORIGINAL COMMENT:
 14- ENGINEER OF RECORD TO SPECIFY ROOF CROSS
 VENTILATION AS REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL.
 NOTE: R-30 BATT INSULATION DOESN'T FIT ON 2X4 ROOF
 JOISTS. ALSO, IT DOESN'T ALLOW ROOF CROSS VENTILATION.
 SEC. R806.3 FBC-RESIDENTIAL.
 ENGINEER MAY DESIGN AN UNVENTED ATTIC. SEE SEC. R806.5
 FBC-RESIDENTIAL AND PROVIDE COMPLETE SPECS SHOWING HOW
 DOING IT.
  
 RESPONSE:
 SPECIFY ROOF CROSS VENTILATION TO COMPLY WITH SEC. R806
 FBC-RESIDENTIAL. SPECIFY VENT SIZE AND LOCATION. SEE
 INSULATION CLEARANCE FOR CROSS VENTILATION. CHECK ROOF
 JOIST SIZE. IF SPECIFYING UNVENTED ATTIC PROVIDE
 COMPLIANCE WITH SEC. R806.5 FBC-RESIDENTIAL. IF USING
 FOAM INSULATION, THEN PROVIDE ICC EVALUATION REPORT
 REVIEWED/APPROVED IN WRITING BY THE ENGINEER OF RECORD.
  
 15- OK.
  
 16- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR IS NOT
 SPECIFYING IF SUBMITTING NOW OR LATER AS DEFERRED
 SUBMITTAL.
  
 B)SLIDING GLASS DOORS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1
 DRAWING.
  
 C)SINGLE HUNG WINDOWS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1
 DRAWING.
  
 D)ENTRY DOOR THAT MEET THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER OF RECORD ON REVISED S.1 DRAWING.
  
 ORIGINAL COMMENT:
 17- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT.
  
 NEW COMMENTS BASED ON REVISED DRAWINGS:
 18- THIS IS NOT ALTERATION LEVEL 2, THIS IS NEW
 CONSTRUCTION. REVISE INFORMATION ON SHEET 2/7 AND SHEET
 S.1.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  