2022-10-21 17:38:49 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22060913 |
| 922 AVON RD |
| |
| ORIGINAL COMMENT: |
| 1- LOT DRAINAGE |
| PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE |
| DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT |
| WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES. |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC. |
| 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| R101.5 FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| RESPONSE: |
| ENERGY CALCULATIONS SUBMITTED: |
| A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM |
| THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS |
| PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| C)CEILING INFORMATION ON ITEM #11 DOESN'T MATCH PLANS. |
| PLANS SHOW VENTED ATTIC AND ROOF INSULATION. |
| NOTE: COORDINATE WITH ENGINEER OF RECORD BECAUSE PLANS |
| WILL NEED TO BE REVISED. THEY ARE NO CORRECT ON TYPE OF |
| VENTILATION AND CEILING INSULATION. SEE COMMENTS BELOW. |
| |
| D) WINDOWS ORIENTATION AND AREA DON'T MATCH PLANS. |
| REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY |
| CONSERVATION. |
| |
| 3- OK. |
| |
| 4- WIND LOAD SCHEDULE. |
| A)OK. |
| |
| ORIGINAL COMMENT: |
| B)ROOF DIAGRAM SHOWN UNDER THE WIND LOAD SCHEDULE |
| DOESN'T CORRESPOND TO ROOF TYPE SHOWN ON PLANS |
| SUBMITTED. SEE FIGURE R301.2(7) FBC-RESIDENTIAL OF |
| CURRENT CODE AND REVISE AS REQUIRED TO MATCH PROPOSED |
| ROOF TYPE. |
| |
| RESPONSE: |
| ROOFS DIAGRAMS SHOWN ON NEW SHEET S.3 DON'T MATCH |
| CURRENT CODE REVISED FIGURE R301.2(7) FBC-RESIDENTIAL. |
| REVISE AS REQUIRED. SHOW ALL NEW ZONES. |
| |
| 5- GUEST HOUSE DIMENSIONS FLOOR PLAN: |
| ORIGINAL COMMENT: |
| A)ENTRY DOOR DOESN'T COMPLY WITH THE MIN. CLEAR WIDTH |
| OF 32" AS REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL. |
| REVISE AS REQUIRED. |
| |
| RESPONSE: |
| COORDINATE WITH ITEM 5(B) BELOW. |
| |
| ORIGINAL COMMENT: |
| B) PROVIDE DOOR AND WINDOW SCHEDULE (NOTE: INCLUDE |
| INTERIOR DOORS). SEC. 107.2.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| DOORS/WINDOWS SHOWN ON THE DOOR/WINDOW SCHEDULES ARE |
| NOT KEYED ON THE FLOOR PLAN. CLEARLY KEY THEM ON BOTH |
| TO AVOID CONFLICTS/CONFUSION. IT LOOKS LIKE THE ENTRY |
| DOOR IS SPECIFIED AS 32" X84" ALU DOOR. THIS DOOR |
| DOESN'T COMPLY WITH THE REQUIRED EGRESS DOOR. ALSO, |
| NEED TO REVISE THE DOOR OPENING DIMENSION SHOWN ON THE |
| GUEST HOUSE DIMENSION FLOOR PLAN. |
| NOTE: COORDINATE INFORMATION ON GUEST HOUSE DIMENSION |
| FLOOR PLAN, DOOR AND WINDOW SCHEDULES (CHECK SIZES) AND |
| NEW PLAN VIEW ON SHEET S.1 TO AVOID MORE |
| CONFLICTS/DELAYS. |
| |
| ORIGINAL COMMENT: |
| C) NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A |
| DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED |
| BY SEC. R320.1.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| 30" DOOR DOESN???T COMPLY. REVISE AS REQUIRED. NEED |
| DOOR THAT PROVIDES 29" MIN. CLEAR OPENING. REVISE AS |
| REQUIRED. TYPICALLY 32" DOORS ARE THE ONES COMPLYING. |
| |
| ORIGINAL COMMENT: |
| 6- PLOT PLAN 1/S1 ON SHEET 1/5: SPECIFY NEW HOUSE |
| CONSTRUCTION SETBACKS TO PROPERTY LINES AND EXISTING |
| MAIN HOUSE. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| HOUSE GUEST HOUSE ADDITION LAYOUT SUBMITTED IS TOO |
| SCHEMATIC. PROVIDE COMPLETE SITE PLAN BASED ON SURVEY |
| SHOWING ACTUAL DIMENSIONS. SEC. 107.3.5.3 CITY |
| AMENDMENTS. |
| |
| 7- GUEST HOUSE ROOF FRAME DETAIL PLAN. |
| |
| ORIGINAL COMMENT: |
| D)SPECIFY ROOF SHEATHING NAILING SPECIFICATIONS TO |
| COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. |
| SPECIFY THICKNESS, NAIL TYPE, SIZE AND SPACING. NOTE: |
| NEED TO USE RING SHANK NAILS. ROOF SHEATHING NEEDS TO |
| BE NAILED AT 4 INCHES O.C. IN THE FIELD AND EDGES AS |
| REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1 |
| FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| SPECIFICATIONS SHOWN ON THE COMPONENT AND CLADDING |
| PRESSURE ZONES ON SHEET S.3. DON'T COMPLY WITH TABLE |
| R803.2.3.1 FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| NTE: COORDINATE WITH ITEM 4(B) ABOVE. |
| |
| 8-12 OK. |
| |
| ORIGINAL COMMENT: |
| 13-R-30 BATT INSULATION DOESN'T FIT ON 2X4 ROOF JOIST. |
| REVISE AS REQUIRED. COORDINATE WITH SPECIFIED CROSS |
| VENTILATION. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| REVISED DRAWINGS DON'T PROVIDE ANY INFORMATION FOR |
| CEILING INSULATION. |
| REVISE TYPICAL WALL SECTION TO INCLUDE: |
| A)CEILING INSULATION TYPE AND R-VALUE. |
| B)WALL INSULATION TYPE AND R-VALUE. |
| |
| ORIGINAL COMMENT: |
| 14- ENGINEER OF RECORD TO SPECIFY ROOF CROSS |
| VENTILATION AS REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL. |
| NOTE: R-30 BATT INSULATION DOESN'T FIT ON 2X4 ROOF |
| JOISTS. ALSO, IT DOESN'T ALLOW ROOF CROSS VENTILATION. |
| SEC. R806.3 FBC-RESIDENTIAL. |
| ENGINEER MAY DESIGN AN UNVENTED ATTIC. SEE SEC. R806.5 |
| FBC-RESIDENTIAL AND PROVIDE COMPLETE SPECS SHOWING HOW |
| DOING IT. |
| |
| RESPONSE: |
| SPECIFY ROOF CROSS VENTILATION TO COMPLY WITH SEC. R806 |
| FBC-RESIDENTIAL. SPECIFY VENT SIZE AND LOCATION. SEE |
| INSULATION CLEARANCE FOR CROSS VENTILATION. CHECK ROOF |
| JOIST SIZE. IF SPECIFYING UNVENTED ATTIC PROVIDE |
| COMPLIANCE WITH SEC. R806.5 FBC-RESIDENTIAL. IF USING |
| FOAM INSULATION, THEN PROVIDE ICC EVALUATION REPORT |
| REVIEWED/APPROVED IN WRITING BY THE ENGINEER OF RECORD. |
| |
| 15- OK. |
| |
| 16- PRODUCT APPROVALS |
| PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| ORIGINAL COMMENT: |
| A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED AND CONTRACTOR IS NOT |
| SPECIFYING IF SUBMITTING NOW OR LATER AS DEFERRED |
| SUBMITTAL. |
| |
| B)SLIDING GLASS DOORS THAT MEET THE DESIGN PRESSURES |
| CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1 |
| DRAWING. |
| |
| C)SINGLE HUNG WINDOWS THAT MEET THE DESIGN PRESSURES |
| CALCULATED BY THE ENGINEER OF RECORD ON REVISED S.1 |
| DRAWING. |
| |
| D)ENTRY DOOR THAT MEET THE DESIGN PRESSURES CALCULATED |
| BY THE ENGINEER OF RECORD ON REVISED S.1 DRAWING. |
| |
| ORIGINAL COMMENT: |
| 17- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| REPEAT COMMENT. |
| |
| NEW COMMENTS BASED ON REVISED DRAWINGS: |
| 18- THIS IS NOT ALTERATION LEVEL 2, THIS IS NEW |
| CONSTRUCTION. REVISE INFORMATION ON SHEET 2/7 AND SHEET |
| S.1. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |