2022-08-01 17:20:13 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22060913 |
| |
| 1- LOT DRAINAGE |
| PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE |
| DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT |
| WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES. |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC. |
| 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| |
| 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| R101.5 FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| 3- FOUNDATION PLAN: |
| A)PROVIDE COMPLETE FOUNDATION PLAN. SEC. R401.2 |
| FBC-RESIDENTIAL. |
| |
| B) SPECIFY MIN. DEPTH AS REQUIRED BY SEC. R403.1.4 |
| FBC-RESIDENTIAL. |
| NOTE: COORDINATE WITH THE WALL SECTION. SHOW DEPTH ON |
| THE WALL SECTION IN RELATION TO THE FINISH GRADE. |
| |
| 4- WIND LOAD SCHEDULE ON SHEET 1/5: |
| A)DESIGN PRESSURES ARE TOO LOW. THE EFFECTIVE WIND AREA |
| IS TOO LARGE. SEE FOOTNOTES ON TABLE R301.2(2) |
| FBC-RESIDENTIAL AND REVISE AS REQUIRED. ALSO, THERE IS |
| A NOTE AT THE BOTTOM RIGHT OF THE TABLE ON SHEET 1/5 |
| STATING "AREA OF COMPONENTS= 50SQF". REVISE THIS NOTE |
| AS WELL. |
| |
| B)ROOF DIAGRAM SHOWN UNDER THE WIND LOAD SCHEDULE |
| DOESN'T CORRESPOND TO ROOF TYPE SHOWN ON PLANS |
| SUBMITTED. SEE FIGURE R301.2(7) FBC-RESIDENTIAL OF |
| CURRENT CODE AND REVISE AS REQUIRED TO MATCH PROPOSED |
| ROOF TYPE. |
| |
| 5- GUEST HOUSE DIMENSIONS PLAN ON SHEET 2/5: |
| A)ENTRY DOOR DOESN'T COMPLY WITH THE MIN. CLEAR WIDTH |
| OF 32" AS REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL. |
| REVISE AS REQUIRED. |
| |
| B) PROVIDE DOOR AND WINDOW SCHEDULE (NOTE: INCLUDE |
| INTERIOR DOORS). SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C) NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A |
| DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED |
| BY SEC. R320.1.1 FBC-RESIDENTIAL. |
| |
| D) PROVIDE COMPLETE DIMENSIONS FOR LOCATION OF DOORS, |
| WINDOWS, HALLWAY WIDTH BETWEEN BATHROOM AND BEDROOM, |
| CLOSET DEPTH, KITCHEN COUNTER-TOPS, ETC. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| 6- PLOT PLAN 1/S1 ON SHEET 1/5: SPECIFY NEW HOUSE |
| CONSTRUCTION SETBACKS TO PROPERTY LINES AND EXISTING |
| MAIN HOUSE. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 7- GUEST HOUSE ROOF FRAME DETAIL PLAN ON SHEET 2/5: |
| A) 2"X4" ROOF JOISTS ARE NOT ADEQUATE TO CARRY THE LIVE |
| AND DEAD LOADS SPECIFIED ON SHEET 3/5. REVISE AS |
| REQUIRED OR ENGINEER TO PROVIDE COMPLETE ENGINEERING |
| ANALYSIS SHOWING COMPLIANCE. SEC. R301.1 |
| FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| B)SPECIFY STRUCTURAL CONNECTOR AT EACH END OF ROOF |
| JOISTS. SEC. R301.2.1 FBC-RESIDENTIAL. |
| NOTE: COORDINATE WITH CONNECTORS SPECIFIED ON SHEET 3/5 |
| ON THE CONNECTOR SCHEDULE. WHO IS THE MANUFACTURER OF |
| THE SPECIFIED CONNECTORS. PROVIDE PRODUCT APPROVAL. |
| FAC. 61G20.3.001. |
| |
| C) ROOF OUTRIGGERS. PROVIDE COMPLETE FRAMING DETAILS |
| AND SPECIFICATIONS, SPECIFY STRUCTURAL FRAMING MEMBER |
| SIZE, SPACING AND CONNECTORS AT EACH END. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| D)SPECIFY ROOF SHEATHING NAILING SPECIFICATIONS TO |
| COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. |
| SPECIFY THICKNESS, NAIL TYPE, SIZE AND SPACING. NOTE: |
| NEED TO USE RING SHANK NAILS. ROOF SHEATHING NEEDS TO |
| BE NAILED AT 4 INCHES O.C. IN THE FIELD AND EDGES AS |
| REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1 |
| FBC-RESIDENTIAL. |
| |
| 8- CONSTRUCTION OF THE NEW BUILDING IS NOT CLEAR. PLANS |
| SUBMITTED HAVE INFORMATION FOR WOOD FRAMED CONSTRUCTION |
| AND CONCRETE BLOCK CONSTRUCTION. PROVIDE ONLY THE |
| INFORMATION RELEVANT TO THIS PROJECT TO AVOID |
| CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 9- DETAIL 4/S1 ON SHEET 2/5 DOESN'T MATCH FLOOR PLAN |
| AND INFORMATION ON DETAIL 6/S1 ON SAME SHEET. REVISE AS |
| REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 10- PROVIDE COMPLETE OPENING FRAMING DETAIL FOR NEW |
| DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS AND |
| CONNECTORS. SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 11- DETAIL 6/S1 ON SHEET 2/5: |
| A)ENGINEER TO CLARIFY WHY IS "NEW NON BEARING WALL |
| DETAILS (TYP)" IF THIS IS AN EXTERIOR WALL. TYPICALLY |
| EXTERIOR WALLS ARE BEARING WALLS. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| B)CORNER DETAIL IS NOT CLEAR AND DOESN'T SEEM TO BE |
| CORRECT. CLEARLY SHOW THE CORNER FRAMING MEMBERS AND |
| HOW THE CORNER IS REINFORCED. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| NOTE: SEE AWC-WCD1-CONVENTIONAL WOOD FRAME DETAILS FOR |
| REFERENCE AND REVISE CORNER DETAIL AS REQUIRED. |
| |
| C)BOTTOM PLATE ANCHORING. SPECIFY HOW MUCH EMBEDMENT IS |
| REQUIRED FOR THE 5/8" ANCHOR BOLT. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| D)SPECIFY ON ALL WALL SECTIONS THE MIN. 6" CLEARANCE |
| FOR TERMITE INSPECTION BETWEEN THE EXTERIOR WALL |
| COVERING AND FINAL EARTH GRADE AS REQUIRED BY SEC. |
| R318.7 FBC-RESIDENTIAL. |
| |
| 12- SHEET 3/5: |
| A) DETAILS 8/S2 AND 4/S2 KEYED ON THE NEW GUEST HOUSE |
| PLAN DETAIL 1/S2 DON'T CORRESPOND TO THIS PROJECT. |
| REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B)SPECIFICATIONS ON DETAIL 5/S2 ARE NOT CLEAR. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| C) DETAIL 3/S2: PROVIDE COMPLETE SPECIFICATIONS FOR THE |
| BOND BEAM. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 13- DETAIL 7/S2 ON SHEET 3/5: |
| A) ASPHALT SHINGLES CAN NOT BE INSTALLED ON A FLAT |
| ROOF. REVISE AS REQUIRED. |
| SEC. R905.2.2 FBC-RESIDENTIAL. |
| |
| B)WALL SECTION IS NOT CLEAR. WHY PROVIDING |
| SPECIFICATIONS FOR WALL STUD AND CONCRETE BLOCK. ALSO, |
| PROVIDE COMPLETE INFORMATION FOR EXTERIOR AND INTERIOR |
| CONSTRUCTION. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C)R-30 BATT INSULATION DOESN'T FIT ON 2X4 ROOF JOIST. |
| REVISE AS REQUIRED. COORDINATE WITH SPECIFIED CROSS |
| VENTILATION. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 14- ENGINEER OF RECORD TO SPECIFY ROOF CROSS |
| VENTILATION AS REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL. |
| NOTE: R-30 BATT INSULATION DOESN'T FIT ON 2X4 ROOF |
| JOISTS. ALSO, IT DOESN'T ALLOW ROOF CROSS VENTILATION. |
| SEC. R806.3 FBC-RESIDENTIAL. |
| ENGINEER MAY DESIGN AN UNVENTED ATTIC. SEE SEC. R806.5 |
| FBC-RESIDENTIAL AND PROVIDE COMPLETE SPECS SHOWING HOW |
| DOING IT. |
| |
| 15- ENGINEER OF RECORD TO SPECIFY HOW PROVIDING HEAT AS |
| REQUIRED BY SEC. R303.10 FBC-RESIDENTIAL. |
| |
| 16- PRODUCT APPROVALS |
| PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL). |
| |
| B)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. |
| |
| C) ALUMINUM VENTED SOFFIT AS SPECIFIED ON PLANS. |
| |
| 17- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 18- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. |
| VALUATION UPDATED TO $60,348. THE PERMIT FEE BALANCE IS |
| $913.04. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |