Plan Review Notes For Permit 22060911 |
Permit Number |
22060911 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2023-02-08 14:57:22 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | 3RD BUILDING REVIEW DENIED: | | | | COMMENT FROM THE LAST BUILDING REVIEW THAT STILL | | REMAINS: | | THERE IS NO BACKFLOW PERMIT FOR THIS PROPERTY. WHAT DO | | YOU PROPOSE FOR DUST CONTROL? | | | | WATERDOWN METHOD: | | IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED | | INFPRMATION OF THE WATER TRUCK SUCH AS: THE | | GALLON CAPACITY OF THE WATER TANK AND A LETTER | | INCLUDING A STATEMENT THAT THE WATER | | USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY | | AND WILL BE ON-SITE AT ALL TIMES | | DURING DEMOLITION. | | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, | | THEN A PARTIAL RELEASE WILL BE NOTED | | ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS | | SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE | | SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE | | BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY | | THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE | | COMPLETED "DEMOLITION APPLICATION" FORM TO | | 561-822-2183. |
|