Plan Review Notes
Plan Review Notes For Permit 22060816
Permit Number 22060816
Review Stop B
Sequence Number 3
Notes
Date Text
2022-08-10 14:31:05JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER; TO CORRECT ALL DATA.
 DATA MUST REFERENCE MIAMI-DADE COUNTY NOA NO.
 20-0110.11 A FLAT ROOF SYSTEM NOT NOA NO. 20-0110.01 A
 METAL PANEL ROOF SYSTEM.
 2. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND
 SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR
 PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL
 LIMITATIONS #7 OF MIAMI-DADE NOA NO.: 20-0110.11.
 PLEASE NOTE THIS PROJECT IS LOCATED IN AN EXPOSURE C
 CATEGORY AREA.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  