2022-09-07 17:57:57 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 22060780 |
| 9/7/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS A601 & P3: THE NEW ACCESSIBLE ROLL-IN SHOWER |
| IS NOT DESIGNED IN COMPLIANCE WITH SEC. AND FIGURE |
| 608.2.2. FBC ACC. A MINIMUM 60-INCH WIDE OPENING IS |
| REQUIRED ON THE FACE OF THE COMPARTMENT, A MINIMUM |
| 30-INCHES WIDE X 60 INCHES LONG CLEAR FLOOR SPACE SHALL |
| BE PROVIDED ADJACENT TO THE OPEN FACE OF THE SHOWER |
| WHICH CANNOT BE OBSTRUCTED BY THE WATER CLOSET- SEC. |
| 2.2.1 FBC ACC. UNDER THE EXCEPTION A LAVATORY COMPLYING |
| WITH SEC. 606 SHALL BE PERMITTED ON ONE 30-INCH WIDE |
| MINIMUM SIDE OF THE CLEARANCE PROVIDED IT IS NOT ON THE |
| SIDE OF THE CLEARANCE ADJACENT TO THE CONTROLS- SEC. |
| 606.2.2.1 FBC ACC. |
| |
| 2) A600 & A601: PROVIDE ACCESSIBLE GRAB BAR AND CONTROL |
| DETAILS FOR THE NEW ROLL-IN SHOWER IN ACCORDANCE WITH |
| SEC. & FIGURE 608.3.2, AND SEC. AND FIGURE 608.5.2 FBC |
| ACC. |
| |
| 3) A100: THE DRINKING FOUNTAINS IN UNIT B ARE |
| PROTRUDING INTO THE CIRCULATION PATH GREATER THAN THE |
| MAXIMUM 4-INCHES ALLOWABLE PER SEC. 307.2 FBC ACC. |
| PLEASE NOTE THAT DRINKING FOUNTAINS WITH CANE APRONS |
| ARE ALLOWED HOWEVER THE FOUNTAINS WERE NOT INCLUDED IN |
| THE FIXTURE SCHEDULE ON SHEET P-1. |
| |
| 4) P-1: THE WATER RISER SHOWS THE IWH-1 WATER HEATERS |
| SUPPLYING LAVATORIES IN UNIT A AND UNIT C WHICH ARE |
| REQUIRED TO DELIVER TEMPERED WATER, NOT HOT WATER- SEC. |
| 419.5 FBC P. PLEASE PROVIDE ASSE 1070 APPROVED MIXING |
| VALVES AT THE LOCATIONS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |